>400kVA Rang
HET 600kVA/35kV Multi-Tap Mobile Test Transformer
1. Electrical Specifications
Parameter | Value |
---|---|
Rated Capacity | 600kVA |
Phase | Single Phase |
Cooling Method | ONAN (Oil Natural Air Natural) |
1.1 Voltage/Current Ratings
Tap Position | Output Voltage | Rated Current |
---|---|---|
S1 | 35kV | 17.1A |
S2 | 25kV | 24A |
S3 | 17.5kV | 34.3A |
S4 | 10kV | 60A |
1.2 Dielectric Test Capability
Withstands 1.1× rated voltage for 1 minute
Partial discharge <5pC at rated voltage
2. Mobile Mechanical Design
Enclosure: Steel housing with integrated wheels
Oil Tank: Shell-type construction
Bushing Configuration:
HV bushings mounted on oil tank
Porcelain bushings for LV connections
Voltage-grade specific terminal bushings
3. Advanced Insulation System
3.1 Bushing Technology
Isovolumetric capacitance core design
Fiberglass-reinforced terminal insulation
Corona rings for 35kV corona-free operation
3.2 Winding Structure
Cylinder-type winding with balanced area design
Compound insulation tube skeleton
Inter-turn insulation layers
Electrostatic shielding between windings
4. Protection Systems
Protection Type | Implementation |
---|---|
Surge Protection | Zinc oxide arresters on all ground connections |
Output Protection | Piezoresistors per HV output |
Flashover Prevention | Main/minor insulation barriers |
5. Oil Management
Oil conservator maintains core immersion
Expansion tank accommodates thermal cycling
25# transformer oil (Grade A)
6. Compliance Standards
IEC 60296 (Transformer Oil Standards)
IEEE C57.12.90 (Test Procedures)
EN 60076 (Power Transformer Requirements)