>400kVA Rang
HET 500kVA/50kV Exciter Transformer - Ultra-High Voltage Testing Solution
The HET 500kVA/50kV,10kV,5kV Exciter Transformer is engineered for extreme high-voltage applications, featuring three precision outputs, laboratory-grade partial discharge performance (<5pC), and military-grade operator protection.
Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 500kVA |
Input Voltage | 3kV |
Input Current | 166.7A |
Output Voltage Ranges | 5kV, 10kV, 50kV |
Output Currents | 50A (5kV/10kV), 10A (50kV) |
Impedance Voltage | <5% |
Partial Discharge | <5pC at rated voltage |
Cooling Method | ONAN (Oil Natural Air Natural) |
Corona-Free Operation | Up to 50kV |
Advanced Design Features
Voltage & Insulation System
Triple-Range Output: 5kV to 50kV coverage for diverse test scenarios
Electrostatic Shielding: Multi-layer isolation between windings
Cylinder Windings: Balanced top/bottom area with shield compensation
Safety & Protection
Dual-Protection System:
Piezoresistor arrays on all HV outputs
Zinc oxide arresters (IEEE C62.11 compliant)
50kV Corona-Free: Fiberglass bushings with isovolumetric capacitance cores
Flashover Prevention: Turn-to-turn insulation withstands 150% surges
Structural Engineering
Mobile Test Platform: Wheel-mounted steel enclosure (1200×800×1600mm)
Advanced Bushings:
HV: Triple-corona-ring fiberglass design
LV: Porcelain bushings per IEC 60137
Oil Management: Conservator with magnetic level indicator
Performance Advantages
Ultra-High Voltage
50kV capability for extreme testing requirements
Micro-Discharge
<5pC ensures measurement accuracy