Technical Specifications
| Parameter | Specification |
|---|---|
| Rated Capacity | 500kVA |
| Input Voltage | 3kV |
| Input Current | 166.7A |
| Output Voltage Ranges | 5kV, 10kV, 50kV |
| Output Currents | 50A (5kV/10kV), 10A (50kV) |
| Impedance Voltage | <5% |
| Partial Discharge | <5pC at rated voltage |
| Cooling Method | ONAN (Oil Natural Air Natural) |
| Corona-Free Operation | Up to 50kV |
Advanced Design Features
Voltage & Insulation System
Triple-Range Output: 5kV to 50kV coverage for diverse test scenarios
Electrostatic Shielding: Multi-layer isolation between windings
Cylinder Windings: Balanced top/bottom area with shield compensation
Safety & Protection
Dual-Protection System:
Piezoresistor arrays on all HV outputs
Zinc oxide arresters (IEEE C62.11 compliant)
50kV Corona-Free: Fiberglass bushings with isovolumetric capacitance cores
Flashover Prevention: Turn-to-turn insulation withstands 150% surges
Structural Engineering
Mobile Test Platform: Wheel-mounted steel enclosure (1200×800×1600mm)
Advanced Bushings:
HV: Triple-corona-ring fiberglass design
LV: Porcelain bushings per IEC 60137
Oil Management: Conservator with magnetic level indicator