100kVA ~ 400kVA Range
HET 300kVA/10kV,6kV,3kV Exciter Transformer - Multi-Range Testing Solution
The HET 300kVA/10kV,6kV,3kV Exciter Transformer is engineered for precision high-voltage testing across multiple voltage ranges, featuring independent HV windings, low-frequency operation (20-300Hz), and advanced safety systems for industrial applications.
Technical Specifications
Parameter | Value |
---|---|
Rated Capacity | 300kVA |
Frequency Range | 20-300Hz (Rated 25Hz) |
HV Winding Voltage | 3kV, 6kV, 10kV (Independent) |
HV Winding Current | 50A (3kV/6kV), 30A (10kV) |
LV Winding Voltage | 2×460V, 2×500V, 2×550V |
LV Winding Current | 2×326A |
Cooling System | ONAN (Oil Natural Air Natural) |
Temperature Rise | Winding ≤65K, Oil ≤55K |
Noise Level | ≤60dB |
Impedance Voltage | <5% |
Advanced Design Features
Core Construction
Premium Core Material: D0130-30 cold-rolled silicon steel with ultra-low Bm value for minimal energy loss
Double-Coil Design: Copper lead wires ensure efficient current transfer
Safety & Monitoring Systems
Electrostatic Shielding: Isolation filter between LV/HV windings prevents interference
Integrated Measurement: HV-side voltage measurement coil for precise monitoring
Oil Management:
Expansion tank with moisture absorber
Oil temperature thermograph and level indicator
Transport & Installation
Robust Shell-Type Design: Oil-immersed construction withstands rigorous transport conditions
Safety-Spaced Windings: Prevents partial discharge and corona effects during operation
Transport-Optimized Components: Bushings, valves, and conservator designed to prevent damage during movement
Performance Advantages
Multi-Voltage Flexibility
Three independent HV outputs (3kV/6kV/10kV) accommodate diverse testing requirements
Frequency Versatility
20-300Hz operational range ideal for various test protocols
Enhanced Safety
Electrostatic shielding and proper winding spacing prevent dangerous discharges
Precision Monitoring
Integrated measurement systems ensure accurate test results
Typical Applications
High-voltage equipment factory acceptance testing
Power transformer and cable diagnostic tests
Frequency-dependent withstand voltage testing
Research and development of high-voltage systems
Why Choose This Transformer?
Test Flexibility: Multiple voltage/frequency combinations for diverse test scenarios
Reliable Performance: Premium materials and design ensure consistent results
Safety Compliance: Meets international standards for high-voltage equipment
Low Maintenance: ONAN cooli