100kVA ~ 400kVA Range
HET 250kVA/16kV Exciter Transformer - Dual-Tap Testing Solution
Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 250kVA (150kVA continuous) |
Frequency | 50Hz |
Tap 1 Output | 0-16kV / 0-9.375A |
Tap 2 Output | 0-8kV / 0-18.75A |
Impedance | <4% |
Cooling | ONAN (25# transformer oil) |
Key Features
Dual-Tap Flexibility
High-voltage tap: 0-16kV @ 9.375A
High-current tap: 0-8kV @ 18.75A
Continuous 150kVA operation
Advanced Protection
Zinc oxide arresters on all terminals
Piezoresistors for each HV output
16kV corona-free bushings
Electrostatic shielding between windings
Robust Construction
Steel housing with integrated wheels
Oil-immersed shell-type design
Fiberglass bushings with corona rings
Isovolumetric capacitance core
16kVMax Voltage
18.75A8kV Output
<4%Impedance
Design Advantages
Cylinder-type winding with balanced area distribution
Compound insulation tube skeleton
Turn-to-turn insulation layers
Electrostatic compensation shielding
Safety Systems
Main/minor insulation protection
Flashover prevention design
Oil conservator with level indicator
Transport-secured components
Typical Applications
Cable withstand voltage testing
Transformer factory acceptance tests
High-voltage component R&D
Switchgear validation
The HET 250kVA/16kV excels in both high-voltage and high-current testing scenarios with its unique dual-tap design, delivering flexible solutions for diverse HV testing requirements.