100kVA ~ 400kVA Range
HET 180kVA Exciter Transformer - High Voltage Testing Solution
Product Overview
The HET 180kVA exciter transformer is a single-phase unit designed for demanding high-voltage testing applications. With multiple output voltage options (4kV, 9kV, 18kV) and wide frequency range (20-300Hz), it serves as a core component in resonant test systems.
Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 180kVA |
Input Voltage | 2×460V / 2×500V |
Output Voltage | 4kV / 9kV / 18kV |
Frequency Range | 20-300Hz |
Cooling Method | ONAN (Oil Natural Air Natural) |
Continuous Operation | 6 minutes at rated capacity |
Key Features
Advanced Safety Protection
Zinc oxide arresters on all HV outputs
Ground-connected input/output terminals
18kV corona-free HV bushings
Integrated piezoresistors for surge protection
Robust Construction
Steel housing with movable wheel base
Shell-type oil tank with conservator
Fiberglass bushings with corona rings
Porcelain bushings for LV connections
Optimized Insulation System
Multi-layer insulation between windings
Electrostatic shielding for voltage distribution
Compound insulation tube winding skeleton
Partial discharge reduction design
Applications
This exciter transformer is ideal for:
Cable withstand voltage testing
GIS and switchgear testing
Transformer factory tests
High-voltage component R&D
Operational Parameters
Temperature Limits: 65°C (windings), 55°C (oil surface)
Sound Level: ≤60dB
Impedance: ≤5%
Insulation Oil: 25# transformer oil
Design Advantages
Our exciter transformer features precision-engineered capacitance grading with:
Balanced top/bottom winding areas
Isovolumetric capacitance core design
Optimized turn-to-turn insulation
Iron coil shielding technology
The HET 180kVA exciter transformer combines robust construction with advanced electrical protection, delivering reliable performance for critical high-voltage testing applications.