High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

100kVA ~ 400kVA Range

HET 100kVA Three-Tap Exciter Transformer | 16kV/11kV/5.5kV Output | 30-300Hz Range

Technical specifications for HET 100kVA exciter transformer with wide frequency range (30-300Hz), triple voltage outputs (16kV/11kV/5.5kV), and <10pC partial discharge.


  • US$ 9,837.00
  • Lead time: 30 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HET 100kVA Three-Tap Exciter Transformer

High-Capacity Variable Frequency Solution

This 100kVA single-phase exciter transformer delivers three selectable high-voltage outputs with wide frequency operation (30-300Hz), designed for demanding testing applications.

Electrical Parameters

ParameterSpecification
Rated Capacity100kVA
Input Voltage350V / 400V / 450V
Output Voltage5.5kV / 11kV / 16kV
Output Current18A / 9A / 6A
Frequency Range30-300Hz
Impedance Voltage≤6%

Performance Characteristics

  • Partial Discharge: <10pC @ rated voltage

  • Insulation Level: GB1094.3-96 compliant

  • Cooling Method: ONAN (Oil Natural Air Natural)

  • Temperature Rise: Winding ≤65K, Oil ≤55K

  • Sound Level: <65dB

Key Technical Features

Voltage Options

  • Three preset output voltages

  • 16kV corona-free operation

  • Adjustable input voltage range

Frequency Characteristics

  • Wide 30-300Hz operating range

  • Continuous 15min operation at rated capacity

  • 1-hour continuous operation within temperature limits

Structural Design

  • Steel housing with wheel-mounted mobility

  • Shell-type oil tank with conservator

  • Copper lead wire winding

Protection System

  1. Electrical Protection:

    • Piezoresistors on all HV outputs

    • Zinc oxide arresters for grounding

    • Fiber glass bushings with corona rings

  2. Insulation System:

    • Electrostatic shield between windings

    • Cylinder winding with turn-to-turn insulation

    • Compound insulation tube skeleton

Technical Specifications

ComponentSpecification
HV BushingFiber glass with corona rings (16kV corona-free)
LV BushingPorcelain insulation
Oil Type25# transformer oil (Class A heat resistance)
WindingAir reactor design with balanced capacitance

Typical Applications

  • Variable frequency resonant testing

  • Power transformer excitation

  • High-voltage cable testing

  • Circuit breaker testing

  • Electrical research laboratories

Safety Compliance

  • GB1094.3-96 insulation standards

  • Flashover protection from external surges

  • Thermal monitoring with automatic protection

  • Isovolumetric capacitance core design

The HET 100kVA three-tap exciter transformer combines flexible voltage outputs with wide frequency operation, delivering reliable performance for demanding high-voltage testing applications.

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message