Most technical literature on dielectric loss testing focuses on power transformers, which hold thousands of liters of oil. Yet instrument transformers, bushings, and tap changers also contain insulating oil—often less than 50 liters—and their oil quality is equally critical. Testing these small-volume devices with an insulating oil dielectric loss tester presents unique challenges that standard procedures do not address.
Current transformers (CTs), voltage transformers (VTs), and oil-filled bushings are essential for protection and measurement. Their oil volumes range from 5 to 50 liters, compared to 5,000 to 50,000 liters for power transformers. Because of the small volume, a fixed amount of contamination has a proportionally larger effect. A few grams of moisture that would be negligible in a large transformer can saturate the oil in a bushing. Additionally, these devices often operate at high electrical stress relative to their size, accelerating oil degradation.
Small-volume equipment presents severe sampling difficulties:
For these reasons, many utilities avoid oil testing on small equipment entirely—a practice that leads to surprise failures. An insulating oil dielectric loss tester requiring only 40 mL of sample enables testing where larger-volume methods cannot be used.
When testing CTs, VTs, or bushings, follow these modified procedures:
For critical bushings, consider installing a permanent sampling port during the next outage to simplify future testing.
Small oil volumes degrade faster and tolerate less contamination. Apply stricter limits than for power transformers:
Note that for some older bushings, oil replacement is impractical or impossible. In these cases, tan δ trending becomes the primary indicator for scheduling replacement of the entire bushing.
In small-volume equipment, moisture ingress is the leading cause of elevated tan δ. Sources include:
For CTs and bushings, moisture content above 20 ppm is a serious concern, and above 40 ppm indicates imminent risk of dielectric breakdown. Karl Fischer titration should accompany every dielectric loss measurement. An insulating oil dielectric loss tester with resistivity measurement adds value here—low resistivity combined with high tan δ strongly indicates moisture.
A 145 kV oil-filled bushing showed tan δ of 0.014 at 90°C with moisture of 45 ppm. The utility had no historical data for this bushing. Comparison with sister bushings on the same circuit showed tan δ of 0.003 and moisture of 12 ppm. The anomalous bushing was replaced during a scheduled outage. Post-mortem inspection revealed degraded gaskets and paper insulation moisture penetration. Without the dielectric loss test, the bushing would likely have failed in service within 12-18 months.
Load tap changer (LTC) oil is separate from main tank oil and requires independent testing. LTC oil is subject to arcing during tap changes, generating carbon particles and acids. Tan δ in LTC oil rises rapidly after switching operations. Test LTC oil every 6 months or after 5,000 operations. Limits are more permissive than main tank oil because arcing by-products are expected, but rising trends still indicate the need for oil change or contact inspection.
When planning small-equipment testing with a portable insulating oil dielectric loss tester, account for:
Instrument transformers and bushings fail less frequently than power transformers, but when they fail, the consequences are severe—protection loss, flashover, and collateral damage. Testing their oil with an insulating oil dielectric loss tester requires modified sampling techniques and stricter interpretation limits, but the effort is justified. Small oil volume means small sample requirements, and modern testers handle 40 mL samples with full accuracy. Add these devices to your oil testing program, and prevent the failures that catch operators by surprise.
Troubleshooting Abnormal Dielectric Loss Results: A Diagnostic Guide for Oil Testing Engineers
Dielectric Loss Testing for Instrument Transformers and Bushings: Small Oil Volume, Big Challenges
Impulse Voltage Testing of Power Transformers Using HV Lightning Impulse Generator Systems
Troubleshooting Common Faults in HV Lightning Impulse Voltage Generator Systems