≤100kV Range
LQTT Series 50kV/200kVA High-Voltage Test Transformer | Precision Testing Systems
The LQTT 50kV/200kVA High-Voltage Test Transformer delivers robust performance for industrial testing applications. Designed as a single-module cylindrical unit, it complies with international standards for dielectric testing, cable/transformer validation, and high-voltage research.
Core Technical Specifications
Parameter | Specification |
---|---|
Rated Capacity | 200 kVA |
Rated Output Voltage | 50 kV AC |
Rated Output Current | 4 A |
Voltage Ratio (Measurement Winding) | 1000:1 |
Frequency | 50Hz / 60Hz |
Waveform Distortion | ≤ 5% (IEC 60060-1) |
No-load Current | ≤ 8% |
Impedance Voltage | ≤ 8% |
Extended Performance Capabilities
Partial Discharge Level: <10 pC at 100% UH (full system)
Overcurrent Withstand: 120% rated current (4.8A) for 300s – no thermal damage
Overvoltage Capability: 110% rated voltage (55kV) for 60s – no insulation failure
Series Operation: Voltage unevenness ≤ ±5% (multiple units)
Operational & Safety Features
HV Grounding: Integrated 5/5 current transformer for live monitoring and operator protection
Thermal Performance:
Winding temperature rise ≤ 65K (above ambient)
Oil surface temperature rise ≤ 55K
Protection System:
0.6kV ZnO arresters on excitation/transfer windings
Oil injection/release valves
Acoustic Noise: ≤ 65 dB(A)
Design & Compliance
Construction: Cylindrical tank (single module)
Dielectric Fluid: #25 Transformer Oil (GB 2536 standard)
Thermal Cycling: Certified for 1-hour continuous operation at 100% UH/IH from ambient temperature