≤100kV Range
Technical Specifications
Electrical Performance
Parameter | Specification | Standard |
---|---|---|
Rated Capacity | 10 kVA | IEC 60076-11 |
Output Voltage | 100 kV AC | |
Output Current | 0.1 A | |
Input Voltage | 0.42 kV (Customizable) | |
Input Current | 23.8 A | |
Frequency | 50 Hz | IEC 60076-1 |
No-Load Current | <10% | IEEE C57.12.00 |
THD | ≤5% | IEC 61000-3-6 |
Impedance Voltage | ≤10% |
Critical Protection Features
Partial Discharge: <5 pC at 100% rated voltage (complete system)
Over-Current Capacity: 150% rated current for 300 seconds (no damage)
Over-Voltage Capacity: 110% rated voltage for 60 seconds
Dielectric Strength: 3 kV/min (LV input to ground)
Thermal Management
Winding Temp Rise: ≤65 K
Oil Temp Rise: ≤55 K
Cooling System: ONAN (Oil-Natural Air-Natural)
Operational Duty:
60 min continuous at 100% rating
Unlimited operation at 80% rating
Physical Properties
Construction: Cylindrical core design
Weight: 100 kg (approx.)
Insulation Fluid: Mineral Oil (Type 25 per GB 2536)
Protection Class: IP54 (IEC 60529)
Key Advantages
✅ High-Precision PD Testing: <5pC sensitivity for critical insulation diagnostics
✅ Exceptional Overload Capacity: 50% current overload for 5 minutes
✅ Optimized Thermal Design: ONAN cooling maintains safety margins during extended tests
✅ Adaptive Input: Customizable primary voltage (0.4kV base + variants)
✅ Dual-Mode Operation: Full-power burst testing + continuous 80% duty