≤100kV Range
Technical Specifications
Electrical Performance
Parameter | Specification | Standard |
---|---|---|
Rated Capacity | 12 kVA | IEC 60076-11 |
Output Voltage | 100 kV AC | |
Output Current | 0.12 A | |
Frequency | 50 Hz / 60 Hz | IEC 60076-1 |
No-Load Current | <10% | IEEE C57.12.00 |
THD | ≤5% | IEC 61000-3-6 |
Impedance Voltage | ≤10% | |
Dielectric Strength | 3 kV/min (LV to ground) | IEC 60270 |
Premium Performance Features
Partial Discharge: <2 pC at 100% UH (complete system) - Industry-best precision
Over-Current Capacity: 150% rated current for 300 seconds (no damage)
Over-Voltage Capacity: 110% rated voltage for 60 seconds
Thermal Management
Winding Temp Rise: ≤65 K
Oil Temp Rise: ≤55 K
Cooling System: ONAN (Oil-Natural Air-Natural)
Operational Duty:
60 min continuous at 100% rating
Unlimited operation at 80% rating
Physical Properties
Construction: Cylindrical core design
Weight: 200 kg (approx.)
Insulation Fluid: Mineral Oil (Type 25 per GB 2536)
Protection Class: IP54 (IEC 60529)
Key Advantages
✅ Ultra-Low PD Sensitivity: <2pC - Precision for critical insulation diagnostics
✅ Superior Overload Capacity: 50% current overload for 5 minutes
✅ Dual-Frequency Operation: Global compatibility (50Hz/60Hz systems)
✅ Thermal Stability: Proven ≤65K rise during extended operations
✅ High-Capacity Compact Design: 12kVA in 200kg package