150kV ~ 400kV
LQHDR Series 350kV/10kΩ/0.25A High Voltage Damping Resistor
Technical Specifications
Parameter | Value | Standard |
---|---|---|
Rated Voltage | 350kV RMS | IEC 60060-1 |
Nominal Resistance | 10kΩ ±3% | IEC 60115-1 |
Rated Current | 0.25A continuous | |
Power Rating | 625W @ 50Hz | (P = I2R = 0.252 × 10,000) |
Continuous Duty | 60min at 100% load | |
Dimensions | Ø350/400 × 1000mm | Tapered design |
Weight | <40kg | |
Power Density | 15.6 W/kg | Industry benchmark |
Temperature Rise | ≤65K at full load | IEC 60076 |
Advanced Design Features
Aerodynamic Profile: Tapered cylindrical design (Ø350→400mm) reduces corona discharge
High Voltage Gradient: Optimized for 3.5kV/mm field distribution
Low-Inductance Construction: <8μH for fast transient response
Integrated Cooling: Longitudinal fins with 30% increased surface area
Corona-Free Terminals: Hemispherical electrodes with RTV coating
Performance Characteristics
Characteristic | Value |
---|---|
Voltage Coefficient | <0.005%/kV |
TCR (Temp Coefficient) | ±100 ppm/°C (-30°C to +85°C) |
Partial Discharge | <2pC @ 350kV |
Step Response | <25ns 10-90% rise time |
Overload Capability | 150% current for 5min |
Mechanical Configuration
Dimensions
Height: 1000mm
Base Ø: 400mm
Top Ø: 350mm
Surface Area: 1.2m²
Terminals
Top: Corona ring (Ø600mm)
Bottom: M16 flange
Ground Lug: M10 stainless
Mounting
Base plate: 4ר18mm holes
Torque: 30Nm ±10%
Orientation: Vertical only
Primary Applications
HV Laboratories
Wavefront shaping in 350kV impulse generators (1.2/50μs)
Transformer Testing
Damping for resonant test systems and partial discharge circuits
Transmission Systems
Surge protection in GIS installations and HVDC converter stations
Installation Requirements
Maintain minimum 2.1m clearance to grounded surfaces (6mm/kV)
Install on insulated platform (≥150kV rating)
Apply dielectric grease to flange connections
Ensure base levelness ≤0.5° deviation
Connect ground using ≥16mm² copper cable
Safety & Compliance
Dielectric test: 420kV AC for 1min (20% overvoltage)
BIL rating: 550kV (IEC 60071-1)
Short-circuit withstand: 8kA peak/100ms
Environmental rating: IP55 (dust/water protected)
Flame resistance: UL94 V-0 compliant
Operational Guidelines
Parameter | Range |
---|---|
Ambient Temperature | -25°C to +40°C |
Relative Humidity | <80% non-condensing |
Altitude | <2000m ASL |
Cooling Recovery | 45min after 60min operation |
Re-energization Delay | Minimum 90min at full cycle |