LQHDR 350kV/10kΩ/0.25A High Voltage Damping Resistor | Compact 625W Design

Compact LQHDR 350kV/10kΩ/0.25A damping resistor with 625W power rating. Designed for 60min continuous operation at full 350kV rating. Cylindrical design (Ø350/400×1000mm) under 40kg weight.


  • US$ 2,469.00
  • Lead time: 30 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHDR Series 350kV/10kΩ/0.25A High Voltage Damping Resistor

Technical Specifications

ParameterValueStandard
Rated Voltage350kV RMSIEC 60060-1
Nominal Resistance10kΩ ±3%IEC 60115-1
Rated Current0.25A continuous
Power Rating625W @ 50Hz(P = I2R = 0.252 × 10,000)
Continuous Duty60min at 100% load
DimensionsØ350/400 × 1000mmTapered design
Weight<40kg
Power Density15.6 W/kgIndustry benchmark
Temperature Rise≤65K at full loadIEC 60076

Advanced Design Features

  • Aerodynamic Profile: Tapered cylindrical design (Ø350→400mm) reduces corona discharge

  • High Voltage Gradient: Optimized for 3.5kV/mm field distribution

  • Low-Inductance Construction: <8μH for fast transient response

  • Integrated Cooling: Longitudinal fins with 30% increased surface area

  • Corona-Free Terminals: Hemispherical electrodes with RTV coating

Performance Characteristics

CharacteristicValue
Voltage Coefficient<0.005%/kV
TCR (Temp Coefficient)±100 ppm/°C (-30°C to +85°C)
Partial Discharge<2pC @ 350kV
Step Response<25ns 10-90% rise time
Overload Capability150% current for 5min

Mechanical Configuration

Dimensions

Height: 1000mm

     Base Ø: 400mm

     Top Ø: 350mm

     Surface Area: 1.2m²

Terminals

Top: Corona ring (Ø600mm)

     Bottom: M16 flange

     Ground Lug: M10 stainless

Mounting

Base plate: 4ר18mm holes

     Torque: 30Nm ±10%

     Orientation: Vertical only

Primary Applications

HV Laboratories

Wavefront shaping in 350kV impulse generators (1.2/50μs)

Transformer Testing

Damping for resonant test systems and partial discharge circuits

Transmission Systems

Surge protection in GIS installations and HVDC converter stations

Installation Requirements

  1. Maintain minimum 2.1m clearance to grounded surfaces (6mm/kV)

  2. Install on insulated platform (≥150kV rating)

  3. Apply dielectric grease to flange connections

  4. Ensure base levelness ≤0.5° deviation

  5. Connect ground using ≥16mm² copper cable

Safety & Compliance

  • Dielectric test: 420kV AC for 1min (20% overvoltage)

  • BIL rating: 550kV (IEC 60071-1)

  • Short-circuit withstand: 8kA peak/100ms

  • Environmental rating: IP55 (dust/water protected)

  • Flame resistance: UL94 V-0 compliant

Operational Guidelines

ParameterRange
Ambient Temperature-25°C to +40°C
Relative Humidity<80% non-condensing
Altitude<2000m ASL
Cooling Recovery45min after 60min operation
Re-energization DelayMinimum 90min at full cycle