150kV ~ 400kV
LQHDR Series 300kV/5kΩ High Voltage Protecting Resistor
Technical Specifications
Rated Voltage: 300kV AC (50/60Hz)
Nominal Resistance: 5kΩ ±3%
Rated Current: 0.2A continuous
Power Rating: 0.2kW continuous
Partial Discharge (PD):
<5pC at 300kV (100% rated voltage)
<3pC at 240kV (80% rated voltage)
Operating Duration: 60 minutes at 300kV/0.2A continuous load
Temperature Rise: <80K on resistor surface at full load
Dimensions: 250mm (W) × 450mm (D) × 1600mm (H)
Weight: <60kg
Termination: Corona-free HV bushings with silicone insulation
Key Performance Features
Compact Footprint: Space-efficient vertical design (1.6m height)
Ultra-Low PD: Triple-shielded construction for sensitive environments
Thermal Efficiency: Advanced heat dissipation maintains
<80k temperature="" rise="">High Dielectric Strength: 350kV withstand voltage for 1 minute
Lightweight Construction: Aircraft-grade aluminum core with composite housing
Application Matrix
Industry | Protection Application | Key Benefit |
---|---|---|
Power Transmission | Transformer bushing protection | Prevents voltage transients |
Test Laboratories | Impulse generator protection | Absorbs reflection waves |
Renewable Energy | Wind turbine converter protection | Suppresses switching surges |
Industrial Manufacturing | X-ray equipment voltage stabilization | Ensures stable DC output |
Installation Specifications
Mounting: Vertical installation on insulated base
Clearances:
1.2m phase-to-phase minimum
1.8m to grounded structures
Environmental Rating: IP55 (suitable for indoor/outdoor use)
Operating Temperature: -30°C to +55°C
Altitude: Full rating up to 2000m ASL
Space-Saving Advantage: The LQHDR-300/5K's compact dimensions (H1600mm) require 40% less installation space than conventional 300kV resistors while maintaining full performance.
Thermal Management System
Passive Cooling: Natural convection design eliminates need for fans
Heat Path: Radial aluminum fins with black anodized coating
Temperature Monitoring: Integrated PT100 sensors (optional)
Safety Margin: Automatic derating above 40°C ambient
Compliance & Standards
IEC 60270:2015 Partial Discharge Measurements
IEC 60060-1:2010 High-voltage test techniques
IEC 60505:2021 Thermal performance evaluation
IEC 61010-1:2010 Safety requirements (CAT IV 300V)
RoHS 3 (EU 2015/863) compliant materials
Maintenance Protocol
Annual Inspection:
Surface contamination check
Resistance verification at 1kV DC
Biennial Testing:
Partial discharge re-certification
Dielectric strength verification at 330kV AC
Cleaning Procedure: Dry compressed air (max 3 bar) or electrostatic wipes
Safety Integration
Install visible discharge indicators on both terminals
Implement interlocked grounding switches
Maintain minimum 1m access clearance around unit
Use HV-rated safety barriers during operation
Perform daily insulation resistance check (>5GΩ)