150kV ~ 400kV
LQHDR Series 300kV/2.5kΩ High-Power Damping Resistor
Technical Specifications
Rated Voltage: 300kV AC (50/60Hz)
Nominal Resistance: 2.5kΩ ±2%
Rated Current: 2A continuous
Power Rating: 10kW continuous (300kV × 2A)
Partial Discharge (PD): <150pC at 100% UH (complete test system)
Operating Duration: 60 minutes at 300kV/2A continuous load
Temperature Rise: <100K on resistor surface at full load
Cooling Requirement: Forced-air cooling mandatory
Standards Compliance: IEC 60270:2015, IEC 60060-1:2010
Key Performance Features
High-Power Capability: 10kW continuous rating for industrial applications
Robust Thermal Design: Optimized heat dissipation maintains < 100K temperature rise
Stable Performance: ±2% resistance tolerance under full load
High di/dt Handling: Withstands rapid current transients up to 100A/µs
Industrial Durability: Stainless steel core with ceramic-coated elements
Application Matrix
Industry | Application | Performance Benefit |
---|---|---|
Power Generation | Generator step-up transformer testing | High-current impulse absorption |
HVDC Transmission | Converter valve testing | DC partial discharge suppression |
Industrial Testing | Circuit breaker short-circuit tests | Arc energy dissipation |
Research Facilities | Pulsed power systems | 10kW continuous load capability |
Cooling System Requirements
Mandatory configuration for full-power operation:
Airflow: 500 CFM minimum (axial or centrifugal)
Ducting: 350mm diameter with smooth interior
Temperature Monitoring: Dual PT100 sensors integrated
Safety Interlock: Automatic shutdown at 130°C core temperature
Coolant Option: Water-cooled terminals available
Thermal Innovation: Features proprietary segmented-core design with interleaved cooling channels that increase heat transfer efficiency by 40% compared to conventional high-power resistors.
Installation Specifications
Mounting Orientation: Horizontal preferred (vertical acceptable)
Clearances:
3.0m phase-to-phase minimum
3.5m to grounded structures
Terminations: Dual M35 flanged connections
Environmental Rating: IP54 (indoor use)
Altitude Derating: 0.8% per 100m above 1000m ASL
Safety & Protection Systems
Integrated over-temperature protection (Class B)
Short-circuit withstand: 40kA/100ms
Dielectric strength: 350kV AC for 1 minute
Flashover protection: Creepage distance >25mm/kV
Fire safety: UL94 V-0 rated materials
Operational Protocol
Pre-cooling: Start cooling system 10 minutes before energization
Ramp-up: Increase voltage at ≤10kV/s rate
Continuous Monitoring: Core temperature (max 120°C), airflow velocity
Cooldown: Maintain airflow for 15 minutes post-operation
Discharge: Use grounded discharge rod before handling
Maintenance Schedule
Frequency | Procedure | Acceptance Criteria |
---|---|---|
Monthly | Visual inspection | No surface discoloration |
Quarterly | Insulation resistance test | >5GΩ at 5kV DC |
Biannual | Resistance verification | ±3% of nominal value |
Annual | Full dielectric test | 350kV AC withstand |
Compliance & Certifications
IEC 61010-1:2010 CAT IV 300V
IEC 60060-1:2010 High-voltage testing
IEEE C57.98-2011 Impulse testing
EN 50191:2010 Erection and operation of test facilities
CE, UKCA, and EAC certified