150kV ~ 400kV
LQHDR Series 300kV/10kΩ/0.5A High Voltage Protecting Resistor
Technical Specifications
Parameter | Value | Standard |
---|---|---|
Rated Voltage | 300kV AC | IEC 60060-1 |
Nominal Resistance | 10kΩ ±5% | IEC 60115-1 |
Rated Current | 0.5A continuous | |
Power Rating | 2.5kW @ 50Hz | Calculated: (0.5A)2 × 10kΩ |
Continuous Operation | 60min at 100% load | |
Dimensions (H×W×D) | 1200 × 420 × 380 mm | |
Weight | <40kg | |
Power Density | 62.5 W/kg | Industry benchmark |
Design Advantages
Compact Form Factor: 30% smaller footprint than comparable 300kV resistors
High Power Density: 62.5 W/kg efficiency rating
Optimized Thermal Management: Natural convection cooling with finned surface design
Low-Inductance Construction: <5μH for transient stability
Corona-Free Operation: Rounded edges and smooth surfaces prevent discharge
Typical Applications
HV Test Circuits
Current limiting in 300kV withstand test setups and partial discharge measurement systems
Power System Protection
Series protection for capacitor banks and transformer bushings
Research Facilities
Wavefront shaping in impulse voltage generators and HV divider networks
Installation & Mounting
Mount on insulated platforms (minimum 150mm creepage distance)
Maintain ≥1.2m clearance to grounded surfaces (per IEC 61958)
Use M12 terminal connectors with 25Nm torque specification
Ensure vertical orientation for optimal thermal performance
Note: Base mounting points provided for 16mm anchor bolts
Performance Characteristics
Condition | Performance |
---|---|
Continuous Operation | 60min @ 300kV/0.5A |
Overload Capability | 150% rated current for 5min |
Temperature Stability | TCR < 200 ppm/°C (-25°C to +85°C) |
Voltage Withstand | 350kV AC for 1min (routine test) |
Safety Compliance
Dielectric strength tested to 350kV AC per IEC 60270
Short-circuit withstand: 10kA/0.2s
Flame-retardant housing (UL94 V-1 rated)
Environmental rating: IP55 (dust protected/water jets)
Maintenance Protocol
Action | Interval |
---|---|
Insulation resistance check | Every 250 operating hours |
Visual inspection (arcing/surface) | Before each use |
Terminal retorquing | Annual |