LQHDR 270kV/5kΩ/0.2A Damping Resistor - Ultra-Low Partial Discharge HV Resistor

Precision 270kV/5kΩ damping resistor with <5pC partial discharge rating. Rated for 0.2A continuous current with 60-minute operation. Compact design (Ø360×8000mm) under 20kg for high-voltage testing applications.


  • US$ 2,170.00
  • Lead time: 30 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHDR Series 270kV/5kΩ High Voltage Damping Resistor

Technical Specifications

  • Rated Voltage: 270kV AC (50/60Hz)

  • Nominal Resistance: 5kΩ ±3%

  • Rated Current: 0.2A continuous

  • Partial Discharge (PD):

    • <5pC at 270kV (100% rated voltage)

    • <3pC at 216kV (80% rated voltage)

  • Operating Duration: 60 minutes at full 270kV/0.2A load

  • Dimensions: Ø300mm (inner) / Ø360mm (outer) × 8000mm

  • Weight: <20kg

  • Termination: Dual corona-reduced HV bushings

  • Standards Compliance: IEC 60270 Partial Discharge Measurements

Key Performance Features

  • Ultra-Low PD Design: Specialized shielding for sensitive measurement environments

  • Precision Waveform Control: Non-inductive winding technique (±0.05µH)

  • Thermal Management: Aluminum oxide-filled epoxy composite for optimal heat dissipation

  • Compact Construction: Highest voltage-to-size ratio in class (270kV in 8m length)

  • Lightweight Solution: 40% lighter than conventional HV resistors

Application Matrix

IndustryTesting ApplicationPerformance Benefit
Power TransformersPartial discharge measurementUltra-low noise for accurate PD detection
Cable SystemsHV cable termination testingPrecise waveform damping
GIS SubstationsSF6 insulation verificationMinimal interference with sensitive equipment
Research LabsHigh-frequency impulse testingStable resistance up to 10kHz

Installation Guidelines

  1. Mount horizontally using V-insulators at 1.5m intervals

  2. Maintain minimum 1.8m clearance to grounded objects

  3. Use silicone-coated HV cables (minimum 300kV rating)

  4. Ground both ends during HV system de-energization

  5. Ambient temperature: -25°C to +50°C operational range

Critical Safety Note: PD measurements require electromagnetic shielding of entire test circuit. Minimum 40dB attenuation recommended for measurements below 10pC.

Compliance & Validation

  • Partial discharge testing per IEC 60270:2015 Class II

  • Dielectric validation per IEC 60060-1:2010

  • Thermal rise certification: ΔT ≤ 65K at 0.2A (IEC 60505)

  • Environmental rating: IP54 (dust and moisture resistant)

  • Quality assurance: ISO 9001:2015 manufacturing

Maintenance Protocol

  • Annual Verification:

    • Resistance tolerance check at 1kV DC

    • Surface contamination test (≤0.05mg/cm²)

  • 3-Year Calibration:

    • Full partial discharge characterization

    • Dielectric strength test at 300kV AC

  • Cleaning Procedure: Non-abrasive, non-conductive cleaners only