High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

100kV ~ 400kV Range

LQTT 250kV/125kVA HV Test Transformer | <2pC PD | Industrial Grade

125kVA industrial test transformer with <2pC PD sensitivity. 250kV/0.5A output, 1500MΩ isolation, 1000:1 measuring winding. For utility/GIS testing. Specs & quote.


  • US$ 24,788.00
  • Lead time: 60 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQTT Series 250kV/125kVA High-Power Test Transformer

(Cylinder Type | Single Phase | Industrial-Grade)


Key Innovations

✅ Unprecedented Power: 125kVA Capacity (5× industry-standard units)
✅ Ultra-Low Partial Discharge:

  • <5pC @ 100% Uₙ (250kV)

  • <2pC @ 70% Uₙ (175kV)
    ✅ Precision Monitoring: 1000:1 Measuring Winding (±0.1% accuracy)
    ✅ Robust Insulation: 1500MΩ inter-winding isolation (IEC 60296 compliant)


Technical Specifications

ParameterValueStandard
Electrical

Frequency50 HzIEC 60076
LV Voltage/Current0.6 kV / 208.3 A
HV Voltage/Current250 kV / 0.5 A
No-Load Current≤10%IEEE C57.12.00
Waveform Distortion≤3%IEC 60060-1
Impedance Voltage≤8%IEC 60076-1
Insulation

HV-LV Ground Isolation1500 MΩIEC 61180
Measuring Winding Ratio1000:1IEC 61869-2
Thermal

Winding Temp Rise≤65 K (80% continuous)IEC 60076-14
Oil Surface Temp Rise≤55 K (80% continuous)IEC 60076-14
Mechanical

Height (w/ Al Electrode)2300 mmISO 9001
Weight2200 kg
CoolingONANISO 2206

Engineering Breakthroughs

  1. Dielectric Superiority

    • Triple-Layer Insulation System:

    • HV ↔ LV: 1500 MΩ  
      HV ↔ Measuring Winding: 1500 MΩ  
      LV ↔ Measuring Winding: 1500 MΩ
    • Exceeds IEEE 1799 requirements for substation-grade equipment

  2. Dynamic PD Performance

    • 175kV operation for <2pC ultra-sensitive diagnostics

    • 250kV operation for production-line testing

    • Voltage-optimized PD suppression:

  3. High-Current Design

    • 100% load (125kVA): 60 min operation

    • 80% continuous load (100kVA): Unlimited runtime

    • 208.3A LV input enables stable 250kV output under:

  4. Advanced Construction

    • Aluminum top electrode: 40% weight reduction vs. steel

    • Cylindrical tank with optimized magnetic flux paths


Target Applications

  • Utility-Scale Testing: Circuit breakers, GIS, 400kV+ transformers

  • Cable Factory QC: Type tests per IEC 60840/62067

  • Research Labs: Dielectric studies at industrial power levels

  • Renewable Energy: HVDC converter transformer validation


Competitive Advantages

► Grid-Ready Power: 125kVA supports cascade configurations up to 750kV
► Measurement Precision: 1000:1 winding enables live calibration without shutdown
► Thermal Resilience: ONAN cooling maintains ≤55K oil rise at 100kVA continuous load
► Safety Compliance: Meets EN 50191 (test station safety) and NFPA 70E (arc-flash)


>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message