150kV ~ 400kV
LQHDR Series 250kV/1kΩ High Voltage Damping Resistor
Technical Specifications
Rated Voltage: 250kV AC/DC
Nominal Resistance: 1kΩ ±5%
Rated Current: 1A continuous
Frequency: 50/60Hz operational
Operating Duration: 60 minutes at full rated load
Temperature Performance: Meets IEC 60076 thermal rise standards at rated current
Termination: Dual shielded HV connectors
Safety Compliance: IEC 61010-1 CAT IV
Core Functions & Design Features
Voltage Stabilization: Suppresses transient oscillations in HV circuits
Impulse Protection: Absorbs lightning impulse voltages up to 250kV
Non-Inductive Design: Wirewound construction with controlled reactance
Thermal Management: Forced-air cooling compatibility for extended operation
Dielectric Housing: Silicone-coated epoxy resin encapsulation
Typical Applications
Application | System Type | Benefit |
---|---|---|
Impulse Voltage Generators | Lightning arrestor testing | Waveform shaping |
Transformer Testing | Dielectric withstand tests | Inrush current limitation |
HV Cable Testing | Partial discharge measurement | Reflection damping |
Research Laboratories | Plasma generation systems | Arc suppression |
Installation & Safety Guidelines
Maintain minimum 1.5m clearance from grounded surfaces
Use only with Class 4 HV leads (300kV rating minimum)
Pre-operational check: Verify insulation resistance >10GΩ at 5kV DC
Thermal monitoring required during continuous 60-minute operation
Post-discharge procedure: Wait 5×RC time constant before handling
Warning: Operate only in temperature-controlled environments (0°C to 40°C)
Compliance & Standards
IEC 60076-14: Power transformer testing
IEEE C57.98-2011: Impulse testing guidance
EN 60204-1: Electrical equipment safety
Temperature rise validation per IEC 60505
Maintenance Protocol
Annual dielectric strength verification at 150% rated voltage
Resistance tolerance check: Quarterly calibration
Surface cleaning: Isopropyl alcohol wipes only
Storage: Humidity-controlled environment (
<40% rh="">