High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

150kV ~ 400kV

LQHDR 200kV/5kΩ/0.05A Damping Resistor | Compact HV Solution | 50Hz Testing

Compact LQHDR 200kV damping resistor with 0.05A rating and 5kΩ resistance. Designed for 1-hour continuous operation in space-constrained HV test setups. Ideal for precision measurements.


  • Negotiated Price
  • Lead time: 30days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHDR 200kV/5kΩ/0.05A Damping Resistor: Compact Solution for Precision HV Testing

Optimized for Space-Constrained HV Applications

The LQHDR 200kV/5kΩ damping resistor delivers essential oscillation suppression in compact high-voltage test environments. Designed for 50Hz systems at 0.05A current, this space-efficient solution (Ф400×1000mm) provides reliable performance in transformer testing, cable diagnostics, and research labs where footprint matters. With its 1-hour continuous operation capability and lightweight design (<40kg), it's ideal for mobile test setups and benchtop configurations.

Technical Specifications

ParameterSpecification
ModelLQHDR 200kV/5kΩ/0.05A
Rated Frequency50Hz
Rated Voltage200kV
Rated Current0.05A
Nominal Resistance5kΩ ±1%
Calculated Power Rating12.5W (I²R = 0.05² × 5000)
Operating Time60 minutes continuous
DimensionsФ350/Ф400 × 1000mm
Weight<40kg

Key Advantages

Space-Optimized Design

With compact Ф400mm diameter and 1000mm length, requires 40% less space than standard HV resistors. Dual-diameter construction optimizes electric field distribution.

Precision Low-Current Operation

Specialized for 0.05A applications where minimal circuit interference is critical. Maintains stable resistance for sensitive measurements in:

  • Partial discharge detection systems

  • Dielectric spectroscopy

  • Calibration reference circuits

Enhanced Portability

Lightweight <40kg construction enables easy integration into:

  • Mobile HV test trailers

  • Benchtop test racks

  • Temporary field testing setups

Typical Applications

ApplicationBenefitStandard Compliance
Transformer PD TestingMinimal circuit loading for accurate measurementsIEC 60270
HV Cable DiagnosticsCompact size for manhole/confined space testingIEC 60502
Research & DevelopmentPrecision reference for experimental setupsIEEE 4
Educational LabsSafe, space-efficient training toolIEC 61010

Installation Guide

Mounting Configuration

  • Vertical Mounting: Preferred orientation (HV terminal upward)

  • Minimum Clearances:

    • 1.2m to grounded surfaces

    • 0.8m to adjacent equipment

Electrical Connections

  • Use silicone-insulated cables (≥200kV rating)

  • Terminal torque: 18-20 Nm

  • Grounding: 16mm² copper wire minimum

Technical Comparison

FeatureStandard HV ResistorLQHDR Compact Model
FootprintØ500-600mmØ400mm
Weight50-70kg<40kg
Min. Current Rating0.1A0.05A
Installation FlexibilityFixed setups onlyMobile/benchtop compatible

Maintenance Protocol

  • Pre-Operation Check: Verify surface cleanliness and terminal integrity

  • Annual Testing:

    • Resistance tolerance verification (±1%)

    • Insulation resistance test (≥1000MΩ)

  • Recalibration: Every 24 months per ISO 17025

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<