100kV ~ 400kV Range
LQTT Series 150kV/15kVA High-Voltage Test Transformer
Ultra-High Voltage Solution for Dielectric Testing & Insulation Verification
Key Advantages
Industry-Leading Voltage: 150kV @ 0.1A - highest voltage class in compact category
Precision PD Performance: <5pC at 100% Uₕ (complete system)
Optimized Portability: 200kg weight - field-deployable design
Robust Thermal Management: ΔT <65K (windings) / <55K (oil) at 80% continuous operation
Technical Specifications
Parameter | Value | Correction |
---|---|---|
Rated Capacity | 15kVA | Compact high-voltage solution |
HV Output | 150kV @ 0.1A | Fixed unit notation (kV) |
Partial Discharge | <5pC @ 100% Uₕ | IEC 60270 compliant |
Input Voltage | 0.4kV (standard) | Customizable available |
Waveform Distortion | ≤5% | IEC 60076-8 compliant |
Impedance Voltage | ≤10% | Optimized regulation |
No-Load Loss | ≤10% | Energy efficient |
Overcurrent Capacity | 150% (0.15A) for 300s | Fixed "150%ln" → 150% Iₙ |
Dielectric Strength | 3kV/min (LV-ground) | Safety compliance |
Operational Profile
1. **OPERATIONAL MODES**
- 100% rating: 60 minutes maximum
- 80% rating: Continuous operation*
*Winding ΔT <65K, Oil ΔT <55K per IEC 60076-11
2. **OVERLOAD PROTECTION**
- 150% current: 300s (winding protected)
- 110% voltage: 60s (insulation protected)
Mechanical & Compliance
Feature | Specification | Standard |
---|---|---|
Cooling System | ONAN (Oil Natural Air Natural) | IEC 60076-14 |
Core Design | Cylindrical | Optimized magnetic circuit |
Frequency | 50Hz | 60Hz optional |
Weight | 200kg | Field-portable |
Insulation Class | H (180°C) | IEC 60085 |