LQHCR 3x50KVA-0.6KV Compensation Reactor: Technical Specifications and Industrial Applications
Core Electrical Parameters
Parameter | Specification |
---|---|
Rated Capacity | 3 × 50KVA (150kVar total) |
Rated Voltage | 0.6kV |
Frequency | 60Hz |
Phase Configuration | Single Phase |
Rated Current Range | 125A - 375A compensation output |
Impedance Voltage | ≤10% |
Critical Safety and Performance Features
Integrated Components
Built-in compensation current transformer (200:5 ratio)
Measurement winding voltage ratio: 1000:1
Robust Overload Capability
Over-current endurance: 10 minutes continuous operation at 120% rated current (450A max) without thermal damage
Over-voltage endurance: 10 minutes operation at 110% rated voltage (0.66kV) without insulation failure
Insulation and Discharge Standards
Insulation test: 5kV/1min (low voltage terminal to earth)
Partial discharge level: ≤10pC
Industrial Applications
This reactor is engineered for:
Power Factor Correction: Compensates reactive power in 0.6kV distribution networks
Harmonic Filtering: Mitigates 5th/7th order harmonics in manufacturing plants
Voltage Stabilization: Regulates voltage fluctuations in mining operations
Renewable Energy Integration: Manages reactive power in solar/wind farm substations
Installation and Maintenance Protocols
Installation Requirements
Ambient temperature: -25°C to +45°C
Altitude: ≤1000m ASL (derate 1% per 100m above)
Clearance: Maintain 500mm ventilation space around units
Maintenance Schedule
Component | Inspection Frequency | Test Method |
---|---|---|
Insulation Resistance | Quarterly | 5kV Megger test |
Connection Integrity | Biannual | Thermographic scanning |
Core Saturation | Annual | Excitation current measurement |
Compliance and Standards
Designed to meet international electrical standards:
IEC 60289: Reactors for power systems
IEEE C57.21: Shunt reactor requirements
EN 60076: Power transformer safety
Warning: Installation must be performed by certified personnel using Category III PPE for 0.6kV systems.