150kV ~ 400kV
LQHDR Series: 150kV/5kΩ High-Voltage Damping Resistor
Critical Transient Suppression for HV Systems
Specialized damping resistors like the LQHDR 150kV/5kΩ model protect high-voltage equipment from destructive transient oscillations. By converting electromagnetic energy into heat, they prevent arc flashes and voltage spikes in circuits exceeding 100kV.
Technical Specifications
Parameter | Value | Standard |
---|---|---|
Rated Voltage | 150kV DC/AC Peak | IEC 60060-1 |
Nominal Resistance | 5kΩ ±10% | MIL-R-26 |
Rated Current | 0.5A Continuous | IEEE 62 |
Operating Time | 60 mins @ 100% load | ANSI C93.1 |
Frequency | 60Hz (50Hz optional) | IEC 60270 |
Key Performance Features
Non-Inductive Design: Minimizes phase shift in measuring circuits
Thermal Stability: ±0.5% resistance drift at full load
Dielectric Strength: 250kV impulse withstand (1.2/50μs wave)
Cooling Recovery: 2-hour cool-down after maximum operating time
Typical Applications
High-Voltage Laboratories
Prevents reflection waves in impulse voltage generators during dielectric testing per IEC 61083-2.
Power Transformer Stations
Damps switching transients in 138kV+ circuit breakers and capacitor banks.
Medical Imaging Equipment
Suppresses X-ray tube discharge oscillations in 150kV generator circuits.
Installation Requirements
Maintain minimum 500mm clearance to grounded surfaces
Ambient temperature ≤40°C (derate 3%/°C above)
Use corona rings above 100kV applications
Verify creepage distance ≥25mm/kV
Compliance & Safety
Designed to meet critical electrical safety standards:
Dielectric testing: IEC 60060-2
Partial discharge: <5pC @ 110kV
Environmental: IP55 (corrosion-resistant housing)
Safety margins: 200% rated voltage for 1 minute
Maintenance Protocol
Ensure optimal performance with:
Monthly: Infrared inspection of terminal connections
Biannual: Resistance tolerance verification
After 500 operations: Full dielectric strength test
Calibration interval: 24 months (NIST-traceable certification available)