150kV ~ 400kV
LQHDR Series: 150kV/0.5kΩ High-Current Damping Resistor (12kW)
Industrial-Grade Power Stabilization
Engineered for extreme electrical environments, the LQHDR 150kV/0.5kΩ/4.9A damping resistor delivers 12kW of robust transient suppression. Featuring nickel-cadmium enameled wire construction and massive heat dissipation capacity, it withstands high-current surges in demanding industrial applications.
Technical Specifications
Parameter | Specification | Standard |
---|---|---|
Rated Voltage | 150kV AC/DC | IEC 60060-1 |
Rated Current | 4.9A Continuous | IEEE 62 |
Nominal Resistance | 0.5kΩ (500Ω) ±10% | MIL-R-26 |
Rated Power | 12,000W (12kW) | IEC 60115 |
Construction | Nickel-Cadmium Enameled Wire | ASTM B355 |
Dimensions | Ø250 × 1550mm | NEMA 250 |
Weight | 65kg | ASTM D642 |
Thermal Design | Forced Air Cooling Required | IEC 60529 |
Robust Performance Features
High-Current Capacity: 4.9A continuous rating for heavy-duty applications
Massive Power Handling: 12kW rating with overload protection
Nickel-Cadmium Construction: Superior thermal conductivity and surge resistance
Industrial Design: Robust Ø250mm cylindrical form factor
High-Temp Operation: Class H insulation (180°C rating)
Industrial Applications
Power Generation
Damps switching transients in 150kV+ generator circuit breakers and excitation systems.
Industrial Rectifiers
Stabilizes high-current DC power supplies for electrolysis and smelting operations.
High-Power Test Systems
Current limiting for 150kV hipot testers and dielectric withstand equipment.
Energy Storage
Controls discharge transients in large capacitor banks and battery systems.
Cooling & Installation Requirements
Thermal Management
Mandatory forced-air cooling with:
Minimum airflow: 500 CFM
Air temperature: ≤35°C intake
Direction: Axial flow through resistor core
Mechanical Installation
Mount vertically with ±1° tolerance
Maintain 800mm clearance to grounded surfaces
Use corona shields for terminals
Install vibration dampers (≥5mm deflection)
Verify creepage distance ≥40mm/kV
Electrical Connections
Terminal Type | Specification | Torque Value |
---|---|---|
HV Input | 150kV silicone-insulated lug | 45 N·m |
Ground | Double-bolt 50mm² copper | 60 N·m |
Cooling Fan | IP56 400V/3ø connector | 25 N·m |
Compliance & Safety
Impulse withstand: 350kV (1.2/50μs wave)
Short-circuit rating: 25kA/1s
Environmental rating: IP54 (outdoor capable)
Safety margin: 200% rated voltage for 1 minute
Arc flash protection: IEEE 1584 Category 4
Maintenance Protocol
Interval | Procedure | Acceptance Criteria |
---|---|---|
Weekly | Cooling system inspection | 500 CFM airflow verified |
Monthly | Terminal infrared scan | ΔT ≤ 30K above ambient |
Quarterly | Resistance measurement | 500Ω ±10% |
Annual | Full dielectric test | Pass 250kV AC/1 min |
Recalibration required every 2000 operating hours.