150kV ~ 400kV
LQHDR Series: 150kV/10kΩ Precision Damping Resistor
High-Voltage Stability in Compact Form
The LQHDR 150kV/10kΩ/0.1A damping resistor delivers precise transient suppression for sensitive high-voltage equipment. With ultra-low partial discharge (lt 5pC) and compact Ø70/115×850mm dimensions, it's ideal for space-constrained 50Hz applications where precision matters.
Technical Specifications
Parameter | Specification | Standard |
---|---|---|
Rated Voltage | 150kV AC/DC | IEC 60060-1 |
Rated Current | 0.1A Continuous | IEEE 62 |
Nominal Resistance | 10kΩ ±5% | MIL-R-26 |
Frequency | 50Hz (60Hz optional) | IEC 60270 |
Partial Discharge | <5pC @ 150kV | IEC 60270 |
Operating Duration | 30 mins @ 100% load | ANSI C93.1 |
Temperature Rise | ≤80K at full load | IEC 60076 |
Dimensions | Ø70/115 × 850mm | NEMA 250 |
Weight | <15kg | ASTM D642 |
Critical Performance Features
Precision Resistance: 10kΩ ±5% tolerance for accurate damping
Ultra-Low PD: <5pC partial discharge protects sensitive equipment
Compact Profile: Ø70/115mm diameter fits confined spaces
Lightweight Design: <15kg for easy installation
Thermal Management: 80K max temperature rise at full load
Targeted Applications
High-Voltage Test Equipment
Stabilizes output in 150kV withstand voltage testers and partial discharge analyzers.
Medical Diagnostic Systems
Damps transients in CT scanner X-ray tubes and linear accelerator circuits.
Research Laboratories
Provides precise damping for particle accelerator components and high-energy physics experiments.
Semiconductor Manufacturing
Suppresses arcs in ion implantation systems and sputtering equipment.
Installation Requirements
Maintain minimum 400mm clearance to grounded surfaces
Ambient temperature ≤35°C (derate 3%/°C above)
Use silicone-coated leads for connections above 100kV
Ensure creepage distance ≥25mm/kV (per IEC 60664-1)
Mount horizontally with 50mm air gap below resistor
Compliance & Safety
Partial discharge: IEC 60270 compliant
Dielectric strength: 220kV lightning impulse (1.2/50μs)
Environmental rating: IP52 (indoor/controlled environments)
Safety margin: 180% rated voltage for 1 minute
Material certification: RoHS 3 compliant
Maintenance Protocol
Interval | Action | Specification |
---|---|---|
Before each use | Visual inspection | No surface contamination |
Quarterly | Resistance verification | 10kΩ ±5% |
Biannual | Infrared thermography | ΔT ≤ 20K above ambient |
24 Months | Full dielectric test | Pass 150kV AC/1 min |
Recalibration recommended every 500 operating cycles or 2 years.