High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Digital PD Detector

LQUP2024 UHF Partial Discharge Tester - 200MS/s 60MHz GIS/Transformer Analyzer

Professional LQUP2024 UHF PD tester with 200MS/s sampling, 60MHz bandwidth, and multi-sensor integration for transformer/GIS/cable partial discharge detection per IEC 60270 standards.


  • US$ 13,116.00
  • Lead time: 30days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQUP2024 Ultra-high Frequency Partial Discharge Detection System

The LQUP2024 represents the next generation of portable PD detection, combining UHF (300MHz-3GHz), ultrasonic, and HFCT sensors with Windows 7 OS for real-time multi-physics analysis of high-voltage equipment defects.

Core Technical Specifications

Measurement Performance
Sampling Rate200MS/s (12-bit ADC)
Bandwidth1Hz-60MHz (±5%)
Input Range0.1mV-20V (12 ranges)
Capacitance Range6pF-250μF

Multi-Sensor Integration

  • UHF Sensor: 300MHz-1.5GHz for GIS internal discharges

  • Ultrasonic Sensor: 20kHz-200kHz for surface tracking

  • HFCT: 1MHz-30MHz for cable sheath currents

  • Combined Sensor: Electric+acoustic for dry-type transformers

Hardware Configuration

Host Unit

  • 6.5" TFT LCD (640×480)

  • Intel 1.6GHz CPU

  • 32GB SSD + 4GB RAM

  • Win7 Embedded OS

Interfaces

  • 2/4× BNC (50Ω inputs)

  • 1× EXT trigger

  • 2× USB 2.0 (mouse/keyboard)

  • Gigabit Ethernet

Detection Methodologies

1. Transformer PD Analysis

Ultrasonic Method

Detects mechanical waves (20kHz-200kHz) propagating through transformer oil with sensitivity to:

  • Winding deformations

  • Bubble discharges in oil

  • Floating component discharges

Pulse Current Method

Measures HF currents (1MHz-30MHz) in core grounding circuits using:

  • Distributed capacitance coupling

  • 100pF-1nF effective sensitivity

2. Switchgear Diagnostics

TEV (Transient Earth Voltage)

Detects ns-level pulses (3MHz-100MHz) escaping through shield gaps:

  • 0.1-10mV typical amplitude

  • Identifies insulation surface tracking

UHF Method

Captures electromagnetic waves (300MHz-1.5GHz) from:

  • Internal corona discharges

  • Floating electrode breakdown

Field Operation Features

ParameterSpecification
Power Options16.8V Li-ion (8hr) / 220V AC
Environmental-20°C to +60°C operation
Portability3kg, 280×190×80mm
Data Storage32GB (≥10,000 waveforms)

Compliance & Applications

  • Standards: IEC 60270, IEEE C57.124, DL/T 1630-2016

  • Typical Use:

    • GIS partial discharge localization

    • Transformer factory acceptance tests

    • Cable joint PD trending

Software Capabilities: Real-time PRPD analysis, phase-resolved mapping, FFT spectrum analysis, and automated report generation with defect classification.

>>>WhatsApp Communication<<<