High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Digital PD Detector

LQPDT2024 Partial Discharge Tester - 16MHz Bandwidth HV Diagnostic System

Professional-grade LQPDT2024 partial discharge tester with 16MHz bandwidth, 80MS/s sampling rate, and dual optical/electrical interfaces for precise HV equipment diagnostics per IEC 60270 standards.


  • US$1.00; Negotiated Price
  • Lead time: 120days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQPDT2024 Partial Discharge Tester Technical Specifications

The LQPDT2024 represents the cutting edge in portable partial discharge detection, combining 16MHz bandwidth with fiber-optic isolation for reliable measurements in high-interference substation environments.

1. Master Acquisition Unit Specifications

1.1 Interfaces & Connectivity

  • Power Input: 6-12V DC (<6W) with locking quick plug

  • Dual Communication:

    • Gigabit Ethernet (RJ45)

    • SFP optical fiber interface

  • Signal Ports:

    • Voltage input (30Hz-500Hz)

    • PD input (5kHz-16MHz)

    • Optional square wave output

1.2 PD Measurement Performance

Bandwidth5kHz-16MHz (±10%)
Input Impedance100Ω/120Ω selectable
Sampling Rate80MS/s (14-bit ADC)
Dynamic Range62dB (7 selectable ranges)
Noise Floor<50μV (self-noise)

1.3 Voltage Measurement

  • 24-bit ADC @ 20kHz sampling

  • 1MΩ input impedance

  • 50V RMS maximum input

2. Power System Configuration

2.1 Dual Power Options

Battery Operation:

  • 7.4V/15Ah Li-ion pack (8hr continuous use)

  • 8.4V/5A fast charging

Direct Power: 8.4V/5A adapter with overvoltage protection

Storage Tip: Maintain full charge when idle, recharge every 3 months

3. Advanced Features

3.1 Test Impedance Unit

  • 17kHz-6MHz bandpass (±10%)

  • 0.5A rated current capacity

  • Overvoltage protection (>50V RMS triggers capacitance adjustment)

3.2 Environmental Durability

Operating Temp-10°C to +60°C
Storage Temp-10°C to +70°C
Humidity≤90% non-condensing

4. Diagnostic Applications

This system is particularly effective for:

  • Transformer PD Mapping: 4-channel synchronous measurement for phase-resolved patterns

  • Cable Termination Testing: 16MHz bandwidth captures high-frequency discharge signals

  • GIS Partial Discharge: Fiber-optic isolation prevents ground loop interference

Compliance & Standards

The LQPDT2024 meets critical requirements of:

  • IEC 60270: High-voltage test techniques - Partial discharge measurements

  • GB/T 7354-2018: Chinese national standard for PD detection

  • IEEE 400.3: Guide for Partial Discharge Testing of Shielded Power Cable Systems

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message