High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Digital PD Detector

LQPDM2025 Partial Discharge Analyzer - Multi-Standard PD Detection System for Transformers & Cables

Advanced LQPDM2025 PD analysis system with single-channel multi-function detection, IEC 60270/IEC 60885-3 compliance, and intelligent interference filtering for precise HV equipment diagnostics.


  • US$ 10,656.00
  • Lead time: 60days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQPDM2025 Partial Discharge Measurement System

The LQPDM2025 represents the pinnacle of digital partial discharge analysis, combining six measurement functions in one compact unit with intelligent interference recognition for reliable field diagnostics.

Standards Compliance

StandardApplication
IEC 60270Basic PD measurement methodology
IEC 60885-3Cable PD testing procedures
DL/T 417Power equipment PD guide
GB/T 16927High-voltage test techniques

Key Features

Measurement Capabilities

  • Single-channel multi-function (equivalent to 6 conventional PD testers)

  • Discharge pulse waveform analysis (time/frequency domain)

  • Real-time 2D/3D PRPD pattern display

Advanced Functions

  • Intelligent interference recognition system

  • Correlation filtering for noise suppression

  • Automatic/manual data recording

Technical Specifications

Measurement Parameters

  • Calibration Range: 5pC-5000pC (8 selectable ranges)

  • Synchronization: Internal/external with phase identification

  • Display Modes: Ellipse, line, sine wave formats

Data Management

Storage Capacity1000+ test cycles
Report GenerationAutomated PDF reports with waveforms
Waveform AnalysisSingle-pulse capture & replay

Typical Discharge Pattern Recognition

Internal Bubble Discharge Characteristics

  1. Discharges occur in 0°-90° and 180°-270° phase ranges

  2. Initial discharge near peak voltage (Un)

  3. Amplitude ratio < 3:1 between half-cycles

  4. Waveform remains stable over time

  5. Discharge rate increases with voltage

Critical Indicator: Sudden amplitude increase (100×) suggests oil-immersed capacitor bubbles

Application Scenarios

Power Transformers

  • Winding turn-to-turn discharges

  • Oil-paper interface tracking

HV Cables

  • Joint partial discharge

  • Water tree degradation

GIS Systems

  • Floating component discharges

  • Particle-induced corona

System Configuration

  • Base Unit: Digital PD analyzer with touchscreen

  • Accessories:

    • Calibrator (5pC-5nC)

    • Test impedance adapters

    • Optical synchronization kit

  • Software: PDMS 2025 analysis suite with:

    • Automatic defect classification

    • Trend analysis tools

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message