>1600KV Range
LQHIVG 3600KV-360KJ Impulse Voltage Generator: Technical Specifications & Testing Capabilities
High-Capacity Impulse Testing Solution
Designed for critical high-voltage infrastructure testing, the LQHIVG 3600KV-360KJ delivers precision impulse generation compliant with IEC 60060-1/2 and IEEE 4 standards. With 360kJ energy capacity and 18-stage configuration, it supports utility-scale testing of transformers, insulators, and switchgear.
Core Technical Specifications
Parameter | Specification |
---|---|
Rated Voltage | ±3600kV |
Stage Voltage | ±200kV |
Charging Voltage | ±100kV |
Rated Energy | 360kJ |
System Capacitance | 0.05555μF (36 × 2μF/100kV capacitors) |
Stages | 18 stages |
Stage Energy | 30kJ |
Synchronization Accuracy | <2% out-of-control rate |
Voltage Stability | <±1.0% fluctuation |
Physical Dimensions | 13.2m height / 10,280kg weight |
Impulse Waveform Capabilities
Standard Waveforms (IEC 60060-1)
Lightning Impulse (Full Wave):
≤4nF load: 1.2μs ±30% / 50μs ±20%
>4nF load: 1-5μs / 40-60μs
Peak oscillation <5%
Switching Impulse: 250μs ±20% / 2500μs ±60%
Chopped Lightning Impulse: 2-6μs chop time
Meets GB311 & GB16927 waveform deviation requirements.
Output Efficiency
Lightning impulse (no load): ≥90%
Lightning impulse (3000pF load): ≥85%
Switching impulse (3000pF load): ≥70%
Operational Parameters
Voltage Range: 15%-100% of rated voltage (Un)
Synchronization: 20%-100% Un with ±1.0% reference deviation
Duty Cycle:
>70% Un: 120s charge/discharge cycle
<70% Un: 90s charge/discharge cycle
Spark Range: 15%-100% Un
Compliance Standards
IEC 60060-1/2 (2010): High-voltage test techniques
IEC 61083-1/2: Digital measurement instruments
ANSI/IEEE 4a (2001): High-voltage testing
IEEE 376 (1975): Impulse strength measurement
ASTM D2518 (Latest): Electrical insulation testing
Industrial Applications
Extra-high-voltage (EHV) transformer certification
Transmission line insulator validation
Substation equipment impulse withstand testing
Renewable energy grid component verification