High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

>1600KV Range

LQHIVG 3600KV-360KJ Impulse Voltage Generator: Technical Specifications & Testing Capabilities

Complete technical specifications of the LQHIVG 3600KV-360KJ Impulse Voltage Generator with IEC/IEEE compliance, waveform parameters, and operational standards for high-voltage testing.


  • US$ 147,541.00
  • Lead time: 120 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHIVG 3600KV-360KJ Impulse Voltage Generator: Technical Specifications & Testing Capabilities

High-Capacity Impulse Testing Solution

Designed for critical high-voltage infrastructure testing, the LQHIVG 3600KV-360KJ delivers precision impulse generation compliant with IEC 60060-1/2 and IEEE 4 standards. With 360kJ energy capacity and 18-stage configuration, it supports utility-scale testing of transformers, insulators, and switchgear.

Core Technical Specifications

ParameterSpecification
Rated Voltage±3600kV
Stage Voltage±200kV
Charging Voltage±100kV
Rated Energy360kJ
System Capacitance0.05555μF (36 × 2μF/100kV capacitors)
Stages18 stages
Stage Energy30kJ
Synchronization Accuracy<2% out-of-control rate
Voltage Stability<±1.0% fluctuation
Physical Dimensions13.2m height / 10,280kg weight

Impulse Waveform Capabilities

Standard Waveforms (IEC 60060-1)

  • Lightning Impulse (Full Wave):

    • ≤4nF load: 1.2μs ±30% / 50μs ±20%

    • >4nF load: 1-5μs / 40-60μs

    • Peak oscillation <5%

  • Switching Impulse: 250μs ±20% / 2500μs ±60%

  • Chopped Lightning Impulse: 2-6μs chop time

Meets GB311 & GB16927 waveform deviation requirements.

Output Efficiency

  • Lightning impulse (no load): ≥90%

  • Lightning impulse (3000pF load): ≥85%

  • Switching impulse (3000pF load): ≥70%

Operational Parameters

  • Voltage Range: 15%-100% of rated voltage (Un)

  • Synchronization: 20%-100% Un with ±1.0% reference deviation

  • Duty Cycle:

    • >70% Un: 120s charge/discharge cycle

    • <70% Un: 90s charge/discharge cycle

  • Spark Range: 15%-100% Un

Compliance Standards

  • IEC 60060-1/2 (2010): High-voltage test techniques

  • IEC 61083-1/2: Digital measurement instruments

  • ANSI/IEEE 4a (2001): High-voltage testing

  • IEEE 376 (1975): Impulse strength measurement

  • ASTM D2518 (Latest): Electrical insulation testing

Industrial Applications

  • Extra-high-voltage (EHV) transformer certification

  • Transmission line insulator validation

  • Substation equipment impulse withstand testing

  • Renewable energy grid component verification

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message