>1600KV Range
LQHIVG 2400KV-360KJ Impulse Voltage Generator: Technical Specifications & Compliance
Product Overview
The LQHIVG 2400KV-360KJ Impulse Voltage Generator is engineered for precision high-voltage testing of electrical insulation systems. With a 2400kV maximum output and 360kJ energy capacity, it simulates lightning strikes, switching surges, and chopping waves to validate equipment resilience under extreme conditions.
Key Technical Parameters
Parameter | Specification |
---|---|
Rated Voltage | +2400kV |
Rated Energy | 360kJ |
Stages | 12 stages |
Stage Voltage | +200kV |
Charging Voltage | +100kV |
Generator Capacitance | 0.125μF (24 x 100kV/3μF units) |
Voltage Utilization | ≥90% (lightning, load <1000pF) ≥85% (lightning, load <3000pF) |
Waveform Accuracy | Oscillation <5% amplitude, dispersity <100ns |
Waveform Capabilities
1. Lightning Impulse Wave (IEC 60060-1)
Waveform: 1.2μs ±30% / 50μs ±20%
Load Range: 400–3000pF
2. Switching Impulse Wave
Waveform: 250μs ±20% / 2500ms ±60%
3. Chopping Wave
Duration: 2–6μs
Dispersity: <100ns
Compliance Standards
IEC 60060-1/2 (2010): High-voltage test definitions & measuring systems
IEC 61083-1/2: Digital recorder requirements for impulse tests
ANSI/IEEE 4a, 376, 1122: Impulse strength measurement protocols
ASTM D2484/D2518: Electrical insulation testing
GB311/GB16927: Chinese national standards
Operational Features
Synchronization: ±20% polarity sync at 20–100% rated voltage
Discharge Control: <2% uncontrolled rate
Voltage Stability: Charging voltage fluctuation <±1.0%
Duty Cycle:
120s cycle at >66% rated voltage
60s cycle at <66% rated voltage
Applications
This generator is essential for:
Transformer and switchgear impulse testing
Power line surge protection validation
Insulation coordination studies (per IEC 60071)
High-voltage component R&D