High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

>1600KV Range

LQHIVG 2400KV-120KJ Impulse Voltage Generator: High-Voltage Testing System

Technical specifications for LQHIVG 2400KV-120KJ Impulse Generator with 12-stage design, 120kJ energy capacity, and compliance with IEC/IEEE standards for high-voltage testing.


  • US$ 93,441.00
  • Lead time: 120 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHIVG 2400KV-120KJ Impulse Voltage Generator: High-Voltage Testing System

Ultra-High Voltage Testing Solution

The LQHIVG 2400KV-120KJ Impulse Voltage Generator delivers industry-leading 2400kV output for demanding high-voltage applications. With its 12-stage modular design and precision waveform generation, this system performs comprehensive testing of electrical insulation systems in compliance with international standards.

Compliance Standards

  • IEC 60060-1/2-2010: High-voltage test techniques & measurement systems

  • IEEE 4a-2001: Standardized high-voltage testing methods

  • IEEE 1122-2007: Digital recording for impulse tests

  • ASTM D2484/D2518: Electrical insulation testing protocols

  • GB311/GB16927: Chinese national standards compliance

Core Technical Specifications

ParameterSpecification
Rated Voltage+2400kV
Stage Configuration12 stages @ 200kV each
Stage Capacitors0.5µF/200kV per stage
Rated Energy120kJ (10kJ/stage)
Voltage Stability< ±1%
Synchronization Error< 2%
Minimum Output≥10% rated voltage

Precision Waveform Generation

Standard Waveforms

  • Lightning Impulse (Full Wave):
     1.2±30%μs / 50±20%μs
      Amplitude tolerance: ±3%
     Peak oscillation ≤5%

  • Switching Impulse:
    250±20%μs / 2500±60%μs

  • Lightning Chopping Wave: 2-5μs

Performance Metrics

  • Output Efficiency:
       Lightning: ≥90% (no load)
       Switching: ≥70% (1000pF load)

  • Waveform compliance: GB311/GB16927 standards

Operational Specifications

  • Voltage Range: 10%-100% of rated voltage

  • Synchronization: ±20% polarity matching across 10-100% range

  • Discharge Cycles:
    >70% voltage: 120s interval
     <70% voltage: Continuous operation

  • Minimum Discharge Time: ≥60s at maximum voltage

  • Sparking Range: 10%-100% Un

Application Areas

  1. High-voltage transformer impulse testing

  2. Switchgear and circuit breaker certification

  3. Insulation system validation for power equipment

  4. High-voltage component R&D stress testing