≤600KVA Range
LQHCR 250KVA-0.6KV Multi-Range Compensation Reactor: Technical Specifications & Thermal Performance
Core Structural Design
Construction: Stationary iron core with protective iron shell
Cooling Method: Natural convection (AN) with thermal monitoring
Voltage Winding: 3kV winding configurable in parallel/series connection
Electrical Specifications
| Parameter | Specification |
|---|---|
| Rated Capacity | 250kVar |
| Rated Voltage | 0.6kV (3kV winding optional) |
| Frequency | 50Hz |
| Phase Configuration | Single Phase |
| Current Ranges | 83.3A, 166.6A, 250A, 333.3A, 416.6A |
| Current Linearity | <+1% deviation |
Performance Characteristics
Robust Overload Capability
Over-current endurance: 10 minutes at 120% rated current (500A max) without damage
Over-voltage endurance: 10 minutes at 110% rated voltage (0.66kV) without insulation failure
Acoustic Performance
Sound pressure level: <65dB at 4m distance (per IEC 60076-10)
Vibration damping: Rubber-mounted core with anti-resonance design
Thermal Management System
| Thermal Parameter | Value | Test Condition |
|---|---|---|
| Winding Temperature Rise | ≤65K | 100% UH for 60 minutes |
| Surface Temperature Rise | ≤55K | 100% UH for 60 minutes |
| Hot Spot Allowance | +15K max over average | Thermal imaging verification |
Insulation Class: Class F (155°C) with Nomex® insulation
Multi-Range Current Applications
| Current Range | Recommended Application | Typical Load |
|---|---|---|
| 83.3A | Small commercial facilities | HVAC systems |
| 166.6A | Medium manufacturing | Conveyor systems |
| 250A | Data center power distribution | UPS systems |
| 333.3A | Heavy industrial plants | Induction furnaces |
| 416.6A | Mining operations | Excavator drives |
3kV Winding Configuration Options
Parallel Connection
Higher current capacity
Reduced voltage per winding
Ideal for high-load industrial sites
Series Connection
Increased voltage handling
Lower current flow
Suited for transmission applications
Note: Configuration change requires certified technician
Installation Requirements
| Parameter | Requirement |
|---|---|
| Operating Temperature | -25°C to +55°C |
| Humidity | <95% RH non-condensing |
| Altitude | <1000m ASL (derate 1.5%/100m above) |
| Foundation Strength | >2000kg/m² load capacity |
Compliance and Testing
IEC 60289: Reactors for AC power systems
IEEE C57.12.01: Dry-type transformer requirements
EN 60076-11: Dry-type transformers
Standard tests include:
Temperature rise validation
Impulse withstand (10kV)
Partial discharge (<10pC)
Maintenance Protocol
Monthly:
Visual inspection of cooling fins
Thermal scan of connections
Quarterly:
Insulation resistance test (5kV Megger)
Winding resistance measurement
Annual:
Full calibration of current ranges
Dielectric absorption test
Acoustic noise verification
Safety Notice: De-energize for 20 minutes before servicing. Use CAT III PPE for 600V systems.










