LQHCR 200KVA-0.6kV Dual-Range Compensation Reactor: Technical Specifications & Design Features
Core Electrical Parameters
Parameter | Specification |
---|---|
Rated Capacity | 200KVA |
Rated Voltage | 0.6kV |
Current Configuration | Dual-range (Position 1: 166.7A, Position 2: 333.3A) |
Corresponding Impedance | Position 1: 3.60Ω, Position 2: 1.80Ω |
Continuous Operation | 60 minutes at 100% rated voltage and current |
Integrated Monitoring System
Built-in Current Transformer: 400:5 ratio for real-time compensation monitoring
Dual-range Selector: Allows precise current matching to load requirements
Thermal Sensors: Embedded in windings for temperature protection
Physical Specifications
Dimension (L×W×H) | 750mm × 450mm × 1500mm |
---|---|
Weight | <1480kg |
Mounting | Floor-standing with anti-vibration pads |
Cable Entry | Bottom entry with IP54-rated bushings |
Note: Clearance of 800mm required on all sides for heat dissipation
Dual-Range Operation Benefits
Position 1 (166.7A)
Optimal for light-load conditions
Higher impedance (3.60Ω) for precise regulation
Ideal for commercial buildings
Position 2 (333.3A)
Designed for peak industrial loads
Lower impedance (1.80Ω) minimizes voltage drop
Recommended for manufacturing plants
Typical Applications
Industrial Machinery: Compensation for high-torque motors in 600V systems
Data Center Power: Reactive power management in critical power infrastructure
Renewable Energy: Voltage stabilization for solar farm inverters
Mining Operations: Power factor correction for excavator drive systems
Installation Requirements
Parameter | Requirement |
---|---|
Ambient Temperature | -20°C to +50°C |
Relative Humidity | <85% non-condensing |
Altitude | <2000m ASL (derate 0.5% per 100m above) |
Foundation | Concrete pad ≥150mm thickness |
Compliance Standards
IEC 60289: Reactors for AC power systems
IEEE C57.12.01: Dry-type transformer requirements
EN 50588: Medium power transformers
Safety certification: UL 508A (Industrial Control Equipment)
Maintenance Protocol
Monthly: Visual inspection of cooling vents
Quarterly:
Torque check on power connections (35Nm ±5%)
CT secondary circuit verification
Annual:
Insulation resistance test (5kV DC Megger)
Impedance measurement at both ranges
Thermal imaging of busbars
Safety Notice: Always discharge for 10 minutes after de-energizing. Use CAT III PPE for 600V systems.