LQHCR 200KVA-0.4KV Iron-Core Compensation Reactor: Technical Specifications & Performance Analysis

Detailed technical specifications of LQHCR 200KVA-0.4KV Iron-Core Compensation Reactor. Includes rated parameters, structural design, overload capabilities, and industrial applications.


  • US$ 4,918.00
  • Lead time: 45 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHCR 200KVA-0.4KV Iron-Core Compensation Reactor: Technical Specifications & Performance Analysis

Core Structural Design

  • Construction Type: Stationary iron core with protective iron shell

  • Cooling System: Natural air cooling (AN classification per IEC 60076)

  • Mounting: Vibration-resistant base frame with anti-corrosion coating

Electrical Specifications

ParameterSpecification
Rated Capacity200kVar
Rated Voltage0.4kV
Frequency60Hz
Phase ConfigurationSingle Phase
Current Ratings125A, 250A, 375A, 500A (selectable ranges)
Current Linearity<+1% deviation across full load range

Performance and Safety Features

Robust Overload Capability

  • Over-current endurance: 10 minutes continuous operation at 120% rated current (600A max) without thermal damage or winding distortion

  • Over-voltage endurance: 10 minutes operation at 110% rated voltage (0.44kV) without insulation failure

Operational Efficiency

  • Acoustic noise level: <70dB at 4m distance (meets ISO 3744 Class B)

  • Core loss: <0.2% of rated power at full load

  • Harmonic distortion: <3% THD at 500A loading

Industrial Applications

  1. Manufacturing Plants: Power factor correction for induction furnaces and CNC machinery

  2. Data Centers: Reactive power management in 400V distribution systems

  3. Renewable Energy: Voltage stabilization in solar inverter output circuits

  4. Marine Power Systems: Harmonic filtering in shipboard electrical networks

Installation and Environmental Specifications

ParameterRequirement
Operating Temperature-25°C to +55°C
Humidity Range<95% RH (non-condensing)
Altitude Limit1000m ASL (1% derating per 100m above)
Clearance Space600mm minimum ventilation perimeter

Compliance and Testing Standards

  • IEC 60289: Reactors for AC power systems

  • IEEE C57.12.01: Standard general requirements for dry-type transformers

  • EN 61558-2-20: Particular requirements for small reactors

  • Routine tests include:

    • Impulse voltage withstand test (10kV peak)

    • Temperature rise verification (Class F insulation)

    • Partial discharge measurement (<10pC)

Maintenance Protocol

  1. Quarterly: Infrared thermography of connections

  2. Biannual: Insulation resistance test (5kV DC Megger)

  3. Annual:

    • Core bolt torque verification (35Nm ±5%)

    • Winding resistance measurement

    • Acoustic noise level validation

Safety Notice: De-energize and ground for 15 minutes before maintenance. Use CAT III PPE for 400V systems.