LQCTT-700kV Cable Test Termination System

Premium testing solution for 700kV ultra-high voltage cables featuring 1650kV impulse capability, precision partial discharge measurement, and extended safety clearances.

Electrical Specifications

  • Rated Voltage: 700kV RMS

  • Partial Discharge Level: <2pC at Un

  • Impulse Voltage Rating: 1650kV (Negative polarity)

  • Power Supply: 220V/20A, 50/60Hz

  • Max. Cable Dimension: 160mm (including insulation)

  • Min. HV Insulation Distance: 3300mm

Cooling System Specifications

ParameterSpecification
Max. Cooling Capacity120kW
Water Capacity500 liters
Max. Operating Temperature60°C
Max. Pressure4 atm
Water Conductivity Range0.1-2 μS/cm
Min. Flow Velocity45 l/min
Connecting Pipe1 inch
Water Pipe Head3/4 inch

Environmental Specifications

  • Ambient Temperature Range: 3°C to 35°C

  • Max. Cooling Water Temperature: 20°C

Physical Dimensions & Configuration

  • Main Unit Dimensions: 1200×1400×1700mm (L×W×H)

  • Base Dimensions: 5800×1400mm (L×W)

  • Terminal Weight: 650kg (for two sets)

  • System Weight: 272kg (without water)

  • Terminal Tilt Angle: 45°

  • Cable Mounting Height: 1600mm

  • Terminal Mounting Height: 5500mm

Advanced Testing Capabilities

  • Ultra-High Voltage Testing: Continuous 700kV operation

  • Lightning Impulse Testing: 1650kV negative polarity

  • Precision PD Measurement: <2pC sensitivity at 700kV

  • Thermal Stress Testing: 60°C temperature validation

  • Pressure Testing: Up to 4 atm pressure conditions

  • Large Cable Testing: Accommodates cables up to 160mm diameter

  • Extended Duration Testing: Sustained operation capability

Industrial Applications

  • Ultra-high voltage cable manufacturing QA

  • National grid transmission system testing

  • HVDC project validation and commissioning

  • Offshore wind farm export cable certification

  • Submarine power link qualification

  • Power infrastructure reliability testing

  • Research institutions high-voltage labs

  • Nuclear power plant cable system validation

Safety & Control Systems

  • Extended Clearance Design: 3300mm minimum insulation distance

  • Intelligent Cooling Control: Adaptive temperature management

  • Water Quality Monitoring: Continuous conductivity measurement

  • Pressure Safety System: Dual-stage venting at 4.1 atm and 4.2 atm

  • Thermal Protection: Quad-redundant shutdown at 62°C

  • Remote Operation: Fiber-optic control interface with safety interlocks

  • Ground Potential Monitoring: Continuous earth resistance verification

  • Atmospheric Monitoring: Humidity and contamination sensors

Installation Requirements

ParameterRequirement
Test Bay DimensionsMin. 18×15m (L×W)
Ceiling HeightMin. 8m (for terminal mounting)
FoundationLevel concrete floor ≥700mm thickness
ClearancesFront: 7000mm, Sides: 4000mm, Rear: 4500mm
Water Supply45 l/min minimum flow rate
Power Connection220V±3%, 20A dedicated circuit
Grounding≤0.15Ω earth resistance
HV ClearanceMin. 3300mm to all objects
Environmental ControlHumidity ≤40% RH, Class 100 cleanroom

Maintenance Protocol

  1. Pre-Test Checks:

    • Verify water conductivity (0.1-2 μS/cm)

    • Confirm cooling flow rate ≥45 l/min

    • Inspect HV terminals for contamination

    • Check atmospheric conditions

  2. Weekly Maintenance:

    • Test all safety interlocks

    • Verify pressure relief valve operation

    • Check terminal contact resistance

    • Calibrate environmental sensors

  3. Monthly Maintenance:

    • Calibrate PD measurement system to IEC 60270

    • Perform dielectric fluid analysis

    • Thermal imaging of HV connections

    • HV bushing partial discharge scan

  4. Annual Certification:

    • Full HV calibration to IEC 60060 standards

    • Pressure vessel recertification

    • Cooling system performance validation

    • Insulation resistance testing at 2000VDC

  5. Biennial Comprehensive Overhaul:

    • Complete disassembly and inspection

    • Replacement of all sealing components

    • Dielectric fluid replacement and filtration

    • Terminal contact refurbishment

Compliance & Standards

  • IEC 60270: High-voltage test techniques - Partial discharge measurements

  • IEC 60885-3: Electrical test methods for electric cables

  • IEEE 400.3: Guide for Partial Discharge Testing of Shielded Power Cable Systems

  • IEC 62067: Power cables with extruded insulation for rated voltages above 150 kV up to 500 kV

  • IEC 60060-1: High-voltage test techniques - General definitions and test requirements

  • IEC 60060-2: High-voltage test techniques - Measuring systems

  • IEC 60060-3: Guidelines for high-voltage testing

  • ISO/IEC 17025: Testing and calibration laboratories

  • CIGRE TB 496: Recommendations for Testing DC Extruded Cable Systems

  • CIGRE TB 722: Testing of HV and EHV AC Extruded Cable Systems

  • CIGRE TB 783: Recommendations for Testing Long Length HV and EHV AC Cables

Certified for ultra-high voltage cable testing in accordance with international standards for transmission-class applications up to 700kV.