Cable Test Terminal
LQCTT-300kV Cable Test Termination System
Advanced cable testing solution designed for 300kV ultra-high voltage cable testing with precision partial discharge measurement and high-capacity cooling system.
Key Electrical Specifications
Rated Voltage: 300kV RMS
Partial Discharge Level: <1pC at Un
Impulse Voltage Rating: 900kV (Negative polarity)
Power Supply: 220V/20A, 50/60Hz
Max. Cable Dimension: 133mm (including insulation)
Min. HV Insulation Distance: 1600mm
Enhanced Cooling System Specifications
Parameter | Specification |
---|---|
Max. Cooling Capacity | 120kW |
Water Capacity | 500 liters |
Max. Operating Temperature | 60°C |
Max. Pressure | 4 atm |
Water Conductivity Range | 0.1-2 μS/cm |
Min. Flow Velocity | 45 l/min |
Connecting Pipe | 1 inch |
Water Pipe Head | 3/4 inch |
Environmental Specifications
Ambient Temperature Range: 3°C to 35°C
Max. Cooling Water Temperature: 20°C
Physical Dimensions & Configuration
Main Unit Dimensions: 1200×1400×1700mm (L×W×H)
Base Dimensions: 3000×1200mm (L×W)
Terminal Weight: 350kg (for two sets)
System Weight: 272kg (without water)
Terminal Tilt Angle: 35°
Cable Mounting Height: 1000mm
Terminal Mounting Height: 2800mm
Advanced Testing Capabilities
Ultra-High Voltage PD Testing: <1pC sensitivity at 300kV
Lightning Impulse Testing: Up to 900kV negative polarity
Extended HV Withstand Testing: Continuous 300kV operation
Thermal Stress Testing: 60°C temperature validation
Pressure Testing: Up to 4 atm pressure conditions
Cable Integrity Testing: For cables up to 133mm diameter
Industrial Applications
EHV cable manufacturing quality assurance
Utility transmission cable commissioning
Offshore wind farm interconnection testing
HVDC cable system validation
Submarine cable certification
Power grid infrastructure testing
Operation & Safety Systems
Dual-Stage Cooling Control: Precision temperature management
Water Quality Monitoring: Real-time conductivity measurement
Pressure Safety System: Automatic venting at 4.2 atm
Thermal Protection: Dual-sensor shutdown at 65°C
Insulation Monitoring: Ensures minimum 1600mm clearance
Remote Operation: Control via isolated interface
Installation Requirements
Parameter | Requirement |
---|---|
Test Bay Dimensions | Min. 8×6m (L×W) |
Foundation | Level concrete floor ≥300mm thickness |
Clearances | Front: 3000mm, Sides: 2000mm, Rear: 2500mm |
Water Supply | 45 l/min minimum flow rate |
Power Connection | 220V±5%, 20A dedicated circuit |
Grounding | ≤1Ω earth resistance |
HV Clearance | Min. 1600mm to all objects |
Maintenance Protocol
Pre-Test Checks:
Verify water conductivity (0.1-2 μS/cm)
Confirm cooling flow rate ≥45 l/min
Inspect termination interfaces
Weekly Maintenance:
Check safety interlocks
Test pressure relief valves
Monthly Maintenance:
Calibrate PD measurement system
Perform dielectric fluid analysis
HV bushing inspection
Annual Certification:
Full HV calibration to IEC 60270
Cooling system performance validation
Insulation resistance testing
Pressure vessel recertification |
Compliance & Standards
IEC 60270: High-voltage test techniques - Partial discharge measurements
IEC 60885-3: Electrical test methods for electric cables
IEEE 400.2: Guide for field testing of shielded power cable systems using very low frequency
IEC 62067: Power cables with extruded insulation for rated voltages above 150 kV up to 500 kV
IEC 60060: High-voltage test techniques
ISO/IEC 17025: Testing and calibration laboratories
Certified for ultra-high voltage cable testing in accordance with international electrical standards.