Cable Test Terminal
LQCTT-400kV Cable Test Termination System
Advanced testing solution for 400kV extra-high voltage cables featuring 1200kV impulse capability, precision partial discharge measurement, and enhanced safety clearances.
Electrical Specifications
Rated Voltage: 400kV RMS
Partial Discharge Level: <2pC at Un
Impulse Voltage Rating: 1200kV (Negative polarity)
Power Supply: 220V/20A, 50/60Hz
Max. Cable Dimension: 133mm (including insulation)
Min. HV Insulation Distance: 1900mm
Cooling System Specifications
Parameter | Specification |
---|---|
Max. Cooling Capacity | 120kW |
Water Capacity | 500 liters |
Max. Operating Temperature | 60°C |
Max. Pressure | 4 atm |
Water Conductivity Range | 0.1-2 μS/cm |
Min. Flow Velocity | 45 l/min |
Connecting Pipe | 1 inch |
Water Pipe Head | 3/4 inch |
Environmental Specifications
Ambient Temperature Range: 3°C to 35°C
Max. Cooling Water Temperature: 20°C
Physical Dimensions & Configuration
Main Unit Dimensions: 1200×1400×1700mm (L×W×H)
Base Dimensions: 3600×1200mm (L×W)
Terminal Weight: 400kg (for two sets)
System Weight: 272kg (without water)
Terminal Tilt Angle: 35°
Cable Mounting Height: 1400mm
Terminal Mounting Height: 3700mm
Advanced Testing Capabilities
Extra-High Voltage Testing: Continuous 400kV operation
Lightning Impulse Testing: 1200kV negative polarity
Precision PD Measurement: <2pC sensitivity at 400kV
Thermal Stress Testing: 60°C temperature validation
Pressure Testing: Up to 4 atm pressure conditions
Large Cable Testing: Accommodates cables up to 133mm diameter
Industrial Applications
Extra-high voltage cable manufacturing QA
Transmission system operator cable commissioning
HVDC interconnection project validation
Offshore wind farm export cable testing
Submarine cable system certification
Power grid infrastructure reliability testing
Safety & Control Systems
Enhanced Clearance Design: 1900mm minimum insulation distance
Intelligent Cooling Control: Dual-stage temperature management
Water Quality Monitoring: Continuous conductivity measurement
Pressure Safety System: Automatic venting at 4.2 atm
Thermal Protection: Triple-redundant shutdown at 65°C
Remote Operation: Isolated control interface with safety interlocks
Installation Requirements
Parameter | Requirement |
---|---|
Test Bay Dimensions | Min. 10×8m (L×W) |
Ceiling Height | Min. 5m (for terminal mounting) |
Foundation | Level concrete floor ≥400mm thickness |
Clearances | Front: 4000mm, Sides: 2500mm, Rear: 3000mm |
Water Supply | 45 l/min minimum flow rate |
Power Connection | 220V±5%, 20A dedicated circuit |
Grounding | ≤0.5Ω earth resistance |
HV Clearance | Min. 1900mm to all objects |
Maintenance Protocol
Pre-Test Checks:
Verify water conductivity (0.1-2 μS/cm)
Confirm cooling flow rate ≥45 l/min
Inspect HV bushings and terminals
Weekly Maintenance:
Test safety interlocks and pressure relief
Check terminal contact surfaces
Monthly Maintenance:
Calibrate PD measurement system to IEC 60270
Perform dielectric fluid analysis
HV bushing partial discharge scan
Annual Certification:
Full HV calibration to IEC 60060 standards
Pressure vessel recertification
Cooling system performance validation
Insulation resistance testing at 500VDC
5-Year Overhaul:
Complete disassembly and inspection
Replacement of all sealing components
Dielectric fluid replacement
Compliance & Standards
IEC 60270: High-voltage test techniques - Partial discharge measurements
IEC 60885-3: Electrical test methods for electric cables
IEEE 400.3: Guide for Partial Discharge Testing of Shielded Power Cable Systems in a Field Environment
IEC 62067: Power cables with extruded insulation for rated voltages above 150 kV up to 500 kV
IEC 60060-1: High-voltage test techniques - General definitions and test requirements
ISO/IEC 17025: Testing and calibration laboratories
Certified for extra-high voltage cable testing in accordance with international electrical standards for transmission-class applications.