Load Capacitor
HRC 300kV/15,000pF Ultra-High Voltage Divider
Classification: Primary reference standard for UHV measurements
Metrological Specifications
Parameter | Specification | Traceability |
---|---|---|
Rated Voltage | 300 kVrms @50Hz | IEC 60358-1 Class AA |
Withstand Voltage | 330 kV/1min (Δtanδ <0.05%) | IEC 60060-1 |
Certified Ratio | 3000:1 (NIST-traceable) | ISO/IEC 17025 |
Partial Discharge | ≤3pC @300kV (≤2pC @240kV) | IEC 60270 Class I |
Precision Characteristics
Electrical Performance
Dielectric Loss: ≤0.2% @20±1°C
Measurement Accuracy: ≤±1%
Phase Defect: ≤0.008°
Operational Limits
Duty Cycle: 1 hour ON / 1 hour OFF
Cooling Method: ONAN
Environment: Indoor (20±5°C)
Mechanical Construction
Insulation System:
Ultra-clean epoxy-oilpaper composite
8-layer capacitive grading
70mm nominal wall thickness
Corona Control:
Ø1000mm quadruple-ring electrode
Surface field ≤12 kV/cm
Mobility System:
Motorized leveling base (±0.25° accuracy)
Air-cushion transport system
Vibration isolation pads
Installation Protocol
Facility Requirements:
8m minimum clearance to ground
Controlled environment lab
±0.5° leveling mandatory
Measurement Setup:
Use 75kV-rated triaxial measurement cable
Double-guard shield connection
Pre-Test Verification:
Step energization (50kV steps, 5min/step)
Baseline PD measurement @200kV
Calibration & Maintenance
Procedure | Interval | Standard |
---|---|---|
Full Ratio Calibration | 6 months | IEC 61869-11 |
Partial Discharge Verification | Quarterly | IEC 60270 |
Oil Condition Analysis | Monthly | ASTM D877 |