High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Load Capacitor

HRC 130kV/36nF Wide-Frequency Capacitive Divider - 1500:1 Ratio (20-300Hz)

Precision 130kV/36,000pF capacitive divider with 1500:1 ratio, 20-300Hz frequency range, and ≤1.5% measurement error for wideband HV testing.


  • US$ 5,056.00
  • Lead time: 30 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HRC 130kV/36,000pF Wide-Frequency Divider

Type: Single-phase capacitive voltage divider (1500:1)

Electrical Specifications

ParameterSpecificationStandard
Rated Voltage130 kVrmsIEC 60358-1
Withstand Voltage143 kV/1minIEC 60060-1
Nominal Ratio1500:1 (certified)IEC 61869-5
Frequency Range20-300 HzIEC 60060-2

Precision Characteristics

Measurement Accuracy

  • Ratio Error: ≤±1.5%

  • Dielectric Loss: ≤0.5% @20°C

  • Phase Error: ≤0.05°

Frequency Performance

  • Low-Freq (20Hz): Derate 5% below 50Hz

  • High-Freq (300Hz): Max ΔT=40°C

  • Capacitance Stability: ±2% full range

Mechanical Design

  • Insulation System:

    • Epoxy-oilpaper composite tube

    • 4-layer capacitive grading

    • Wall thickness: 32mm

  • Dimensions: Ø350×1800mm

  • Weight: ≈350 kg (operational)

  • Mobility:

    • 4× industrial casters (300kg capacity)

    • Quick-release base with transport locks

Installation & Operation

  1. Clearance Requirements:

    • 3.8m minimum to ground

    • 2.2m vertical clearance

  2. Measurement Setup:

    • Use 30kV-rated triaxial measurement cable

    • For two-stage: match cable lengths within 0.4m

  3. Frequency Adaptation:

    • Below 50Hz: Reduce voltage by 1%/Hz

    • Above 150Hz: Limit to 90% rated voltage

Certification & Maintenance

ItemRequirement
Calibration CycleAnnual (or 500 operating hours)
Oil InspectionEvery 6 months (IEC 60422)
Dielectric TestBiannual @100kV

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message