Load Capacitor
HRC 120kV/9,000pF Reference Standard Capacitor
Configuration: Single-stage design for precision measurements
Electrical Specifications
Parameter | Specification | Standard |
---|---|---|
Rated Voltage | 120 kVrms @50Hz | IEC 60358-1 |
Withstand Voltage | 132 kV/1min (110%) | IEC 60060-1 |
Nominal Capacitance | 9,000 pF ±1% | IEC 60384-1 |
Partial Discharge | <1 pC @120kV | IEC 60270 Class I |
Precision Performance
Measurement Accuracy
Dielectric Loss: ≤0.2% @20°C
Voltage Ratio Error: ≤±1%
Phase Angle Stability: <0.01°/h
Thermal Management
Duty Cycle: 1 hour ON / 1 hour OFF
Temp Coefficient: <25 ppm/°C
Cooling: Natural convection (ONAN)
Mechanical Construction
Insulation System:
Epoxy-oilpaper composite tube
4-layer capacitive grading
Wall thickness: 30mm nominal
Dimensions: Ø300/400×1850mm
Weight: 300 kg (including base)
Mobility:
4× heavy-duty casters (200kg capacity each)
Quick-disconnect base mechanism
Installation Protocol
Site Preparation:
3.5m minimum clearance to grounded objects
Level surface within ±2°
Measurement Setup:
Use supplied 30kV-rated double-shielded cable
Ground shield at source end only
Thermal Conditioning:
Pre-heat to ambient +5°C before testing
Monitor oil temperature (max 60°C)
Operational Limits
Parameter | Limit |
---|---|
Continuous Operation | 60 minutes maximum |
Cooling Period | 60 minutes minimum |
Daily Cycles | 6 maximum |
Ambient Humidity | <70% RH (non-condensing) |