Gas Insulated Test Transformer
HGTS 325KV/162.5KVA SF6 Gas Insulated Test Transformer
Engineered for demanding high-voltage testing scenarios, this advanced SF6-insulated transformer delivers precision performance with dual-voltage flexibility and comprehensive safety monitoring.
Key Technical Specifications
Rated Capacity: 162.5kVA
Voltage Configuration: Dual-range output (162.5KV/325KV)
Current Ratings: LV: 2×135.4A / HV: 0.5A
Partial Discharge: ≤5pC at 100% rated voltage
Waveform Accuracy: <3% deviation
Dual-Voltage Operation System
Serial Connection (Precision Mode)
Output: 162.5KV/0.5A
Ideal for extended duration tests
Optimal for partial discharge measurements
Parallel Connection (High Voltage Mode)
Output: 325KV/0.5A
Maximum voltage capability
For insulation withstand testing
Advanced Performance Features
Parameter | Specification |
---|---|
Impedance Voltage | <20% |
No-load Current | <10% |
Dielectric Loss | <0.5% |
Noise Level | <65dB |
Overcurrent Withstand | 0.6A for 300s |
Overvoltage Capability | 357.5KV for 60s |
Specialized Load Cycling Capabilities
Standard Test Cycles
800pF load: 275KV, 15min on/15min off (8 cycles/day)
2000pF load (high): 275KV, 2min on/15min off (8 cycles/day)
2000pF load (low): 145KV, 15min on/15min off (8 cycles/day)
Integrated Safety Systems
Current Monitoring Protection
5/5 CT supervision on HV terminal
Real-time earth current monitoring
Operator safety guarantee system
Surge Protection
0.6kV surge arrestors on exciting winding
Withstands 3×275KV discharge tests
Damping resistor protection
Laboratory & Industrial Applications
High-voltage cable testing
Transformer factory acceptance tests
Partial discharge research
Insulation material development
Electrical component endurance testing
Operational Guidelines
For optimal performance and transformer longevity:
Adhere strictly to specified load cycling times
Monitor SF6 pressure before each test series
Verify CT monitoring system functionality
Allow proper cooling between test cycles