Gas Insulated Test Transformer
HGTS 1200KV/1200KVA SF6 Gas Insulated Test Reactor
This ultra-high voltage test reactor sets new standards with <1pC partial discharge performance at 750KV and 3200H precision inductance (±10%/+5%) in a compact SF6-insulated design.
Electrical Specifications
Rated Capacity: 1200KVA
Test Voltage: 1000KV standard (1200KV rated)
Rated Current: 1A
Inductance: 3200H (±10%/+5%)
Frequency: 50Hz
Performance Metrics
Partial Discharge: <1pC @ 750KV
Insulation Level: 1.05× rated voltage for 1min
Duty Cycle: 20min on/60min off (8× daily)
SF6 Gas Insulation System
Parameter | Value |
---|---|
Rated Pressure | 0.45-0.5MPa |
Max Pressure | <0.8MPa |
Max Temperature | <40°C |
Installation | Sealed capacitor design |
Precision Testing Capabilities
Ultra-Low Partial Discharge
<1pC at 750KV (62.5% of rated voltage)
Ideal for sensitive insulation tests
Laboratory-grade accuracy
Stable Inductance
3200H nominal value
-10%/+5% tolerance range
Consistent performance across cycles
Operational Guidelines
Duty Cycle: Maximum 8 cycles/day (20min operation + 60min cooldown)
SF6 Monitoring: Verify pressure (0.45-0.5MPa) before each test
Temperature Control: Maintain gas temperature <40°C
Safety Margin: 1.05× voltage withstand for 1min
Research & Industrial Applications
High-Voltage Research
Insulation material development
Partial discharge studies
Ultra-HV component testing
Industrial Testing
Power transformer validation
GIS equipment qualification
High-voltage cable testing
Why This Reactor Stands Out
Industry-leading <1pC PD performance
Precision 3200H inductance control
Advanced SF6 gas insulation system
Robust 20min/8-cycle operation
Ultra-HV 1200KV capability