Monitoring
LQ610 DC High-Voltage Generator
*Arrester & Cable Testing | GB 11032-89 Compliant | Field-Ready Reliability*
Engineered for Critical DC Withstand Tests
The LQ610 is a next-generation DC HV generator designed for voltage withstand testing and leakage current measurement of metal-oxide arresters (MOA), power cables, and high-voltage equipment. Fully compliant with China's GB 11032-89 standard for no-gap ZnO arresters, it replaces legacy systems with advanced safety and portability.
Key Technical Innovations
Feature | Technical Advantage | User Impact |
---|---|---|
High Power Density | 50% smaller, 40% lighter vs. predecessors | One-person transport & deployment |
Triple Protection | Over-voltage + Over-current + Zero-start cutoff | Prevents operator/equipment hazards |
0.75U₁ Storage | Auto-captures leakage current at 75% max voltage | MOA degradation analysis (GB 11032) |
Programmable Timer | 1–60 min tests + audible alarm | Hands-free operation |
Military-Grade Components | Silicon carbide HV rectifiers | 100,000+ test cycles reliability |
Intuitive Interface | Digital kV/mA display + rotary control | Zero training time |
Technical Specifications
Parameter | Specification |
---|---|
Output Voltage | 0–120 kV DC (5 kV steps) |
Max Current | 5 mA (continuous) |
Ripple Factor | <1% (per IEC 60060-1) |
Voltage Stability | ±0.5% (0–100% load) |
0.75U₁ Function | Auto-triggered storage & display |
Timer Range | 1–60 minutes (1s resolution) |
Safety Standards | GB 311.1, IEC 61010-1 CAT IV 120kV |
Compliance & Applications
Standards Met
GB 11032-89: No-gap metal oxide arresters
DL/T 474.4-2018: DC withstand test procedures
IEC 60060-1: HV test techniques
Critical Tests Performed
Equipment | Test Type | LQ610 Function |
---|---|---|
ZnO Arresters | Leakage current @ 0.75U₁ | Auto measurement + storage |
HV Cables | DC withstand test | Ramped voltage + timer |
Transformers | Insulation resistance | Constant voltage leakage monitoring |
Switchgear | Polarity verification | Negative/positive DC output |
Workflow: Arrester Testing Example
Connect
Clip HV lead to arrester top terminal
Ground base plate
Program
Set Uₘₐₓ (e.g., 100kV for 110kV arrester)
Enable 0.75U₁ (75kV auto-capture)
Ramp
Increase voltage to Uₘₐₓ at 1kV/s
Hold
10-minute timer starts (audible alert at end)
Analyze
Record leakage current at 0.75U₁ (acceptance: <500μA)
Safety Systems
Zero-Start Interlock
Prevents energization if control knob ≠ "0"Emergency Cutoff
<0.1ms shutdown on arc detectionAutomatic Discharge
Bleeds stored energy to <5V after testDual Grounding
Redundant earth terminals (EN 50191)