Monitoring
Capacitance & Tan Delta Tester
Integrated HV Diagnostics | Variable Frequency Testing | Oil & Solid Insulation Analysis
All-in-One Insulation Assessment
This advanced tester combines capacitance (Cx) and dielectric loss (tan δ) measurement in a single integrated platform, featuring built-in HV generation, SF6 reference capacitor, and frequency conversion for precise insulation diagnostics per IEC 60250.
Core System Components
Component | Function | Technical Advantage |
---|---|---|
Variable Frequency Power | 30–300Hz adjustable output | Eliminates interference from grid harmonics |
Boosting Transformer | Generates 10kV AC (max) | Direct testing without external HV source |
SF6 Standard Capacitor | NIST-traceable reference (100pF ±0.05%) | Ensures ±0.1% tan δ accuracy |
Test Bridge | Automated Schering bridge circuit | Measures Cx and tan δ simultaneously |
Inverter HV Source | Clean sine wave (<0.5% THD) | Prevents measurement distortion |
Key Specifications
Parameter | Specification |
---|---|
Capacitance Range | 1 pF – 1 μF |
Tan δ Resolution | 0.0001 |
Test Voltage | 0.5–10 kV AC |
Frequency Range | 30 Hz – 300 Hz (1 Hz steps) |
Accuracy | ±(0.5% Cx + 0.5 pF), ±(1% tan δ + 0.0001) |
Temperature Control | Optional: -20°C to +100°C (oil tests) |
Safety Compliance | IEC 61010-1 CAT IV 10kV |
Testing Capabilities
1. Solid Insulation Diagnostics
Transformers/Bushings: Detects moisture ingress & insulation aging
Cables/GIS: Identifies voids & delamination
Surge Arresters: Measures ZnO degradation
2. Insulating Oil Analysis (with Accessories)
Accessory | Function | Standard |
---|---|---|
Insulation Cup | Precision oil test cell | IEC 60247 |
Peltier Heater | Temperature stabilization (±0.5°C) | ASTM D924 |
Agitation System | Eliminates bubbles during testing | ISO 3013 |
Workflow: Automated Testing
Connection
Connect test object to HV/LV terminals
Frequency Optimization
Auto-selects 40/50/60Hz or sweeps for resonance avoidance
Measurement
Applies voltage → computes Cx/tan δ in <15 seconds
Diagnostics
Flags deviations from IEEE 286 thresholds
Reporting
Prints IEC 60505-compliant pass/fail certificates
Critical Applications
Equipment | Test Voltage | Acceptance Threshold | Fault Detected |
---|---|---|---|
Transformer Bushings | 10 kV | tan δ ≤ 0.005 @ 20°C | Moisture ingress >15 ppm |
HV Cables | 2–5 kV | ΔCx ≤ 1% (Y-Y) | Shield deterioration |
Generator Stators | 6–10 kV | tan δ ≤ 0.02 @ 130°C | Thermal aging of epoxy mica |
Insulating Oil | 1 kV | tan δ ≤ 0.001 @ 90°C | Oxidation byproducts |
Competitive Advantages
Conventional Testers | This Solution |
---|---|
Separate HV source required | All-in-one design (no external gear) |
Fixed 50/60Hz testing | Variable frequency for noise immunity |
Manual bridge balancing | Auto-calibration in 3 seconds |
No oil testing capability | Integrated oil analysis with add-ons |