Key Specifications
Electrical Ratings
Rated Capacity: 12 kVA
Input Voltage: 380 V AC (±15% typical)
Output Voltage: 0-420 V AC (Continuously adjustable)
Input Current: 31.6 A (Rated)
Output Current: 0-28.5 A
Frequency: 50 Hz
Waveform Distortion: ≤3% THD
Regulation & Protection
Regulation Type: Servo-Driven Contact Mechanism
Short-Circuit Withstand: 2× rated current (57A) for 8 cycles (160ms @50Hz) without damage
Position Limits: Upper/lower limit switches with cut-off protection
Duty Cycle:
✓ 60 min at 100% voltage & current
✓ Continuous operation at 80% rated loadConstruction & Safety
Damping resistor for capacitive discharge protection
Mechanical winding protection against deformation
Transformer short-circuit reinforcement
Cooling: ONAN (Oil Natural Air Natural)
Critical Safeguards:
Weight: 60 kg (robust industrial design)
Core Technology Advantages
Industrial-Grade Resilience: Engineered to withstand 200% overload transients during test object discharges
Zero-Damage Protection: Reinforced windings and damping systems prevent mechanical stress during faults
Precision Control: Linear 0-420V adjustment via servo-driven contact mechanism
Operational Flexibility: Dual operating modes (full power intermittent / 80% continuous)
Safety Compliance: Position limiters prevent overtravel damage