100kv ~ 200kV Range
LQHVF 120kV/1000pF Portable Voltage Divider
Industry's lightest 120kV-class measurement solution featuring breakthrough portability without compromising accuracy. Engineered for field testing teams requiring high-voltage measurement in substations, renewable sites, and remote locations.
Technical Specifications
Rated Voltage: 120kV AC RMS
Nominal Capacitance: 1000pF
Dividing Ratio: 1000:1 (±1% accuracy)
Frequency: 50/60Hz (45-500Hz range)
Dielectric Loss: <0.5% @ 25°C
Partial Discharge: <5pC at 120kV
Cooling System: ONAN (Oil Natural Air Natural)
Operating Duration:
60 minutes continuous @ 100% rated voltage
Unlimited operation @ 80% rated voltage
Dimensions: Base Ø150mm / Top Ø500mm × 1100mm height
Weight: <30kg (lightest in class)
Portable Structural Design
Compact Oil-Immersed Architecture
Removable Base: Enables field maintenance without depot return
Corona Rings: Dual aluminum alloy rings prevent discharge
LV Arm: Low-voltage interface with weatherproof connectors
HV Arm: Precision capacitive stack with space-optimized design
Transport Optimized: 40% lighter than comparable 120kV dividers
Field Deployment Features
Integrated Carrying Handles: Ergonomically positioned for single-person transport
Quick-Assembly System: Field-ready in <8 minutes
Tripod-Compatible Base: Standard 3/8"-16 mounting thread
Stackable Design: Nests for efficient vehicle storage
Performance Validation
Parameter | Test Standard | Performance |
---|---|---|
Voltage Withstand | IEC 60060-1 | 144kV/1min (120% rated) |
Linearity Error | IEC 61869-11 | <±0.9% 10-100% range |
Temperature Rise | IEEE C57.19.00 | 40°C above ambient @ full load |
Vibration Resistance | IEC 60068-2-6 | 6g @ 10-150Hz |
Compliance: Meets IEC 61869-11, IEEE C57.13, and ANSI/NETA MTS-2023 standards.
Field Applications
Mobile Substation Testing
Circuit breaker timing tests
Protective relay calibration
Transformer ratio verification
Renewable Energy Sites
Solar farm combiner monitoring
Wind turbine step-up transformers
Battery storage system validation
Industrial Maintenance
Rotating machinery testing
Cable fault location
Ground grid integrity verification
Operational Advantages
Ultra-Lightweight: <30kg enables single-person transport
Rapid Deployment: Field-assembly in <8 minutes
Maintenance Optimized: Removable base reduces service downtime by 65%
Environmental Resilience: IP54 rating for field conditions
Cost Efficient: 45% lower shipping costs than standard dividers
Field Deployment Protocol
Setup Procedure
Position on stable surface or tripod mount
Assemble corona rings and HV/LV arms
Establish dual-point grounding (≤0.1Ω resistance)
Connect LV measurement leads to test set
Implement HV corona-free connection
Perform safety verification at 20% rated voltage
Transportation Guidelines
Maximum Tilt: 30° during transport
Temperature Range: -20°C to +50°C
Shock Protection:
Use included foam inserts
Max drop height: 15cm
Packaged Dimensions: 600×600×1300mm (L×W×H)
Safety & Maintenance
Field Safety Procedures
Establish 2.5m safety perimeter per IEEE 516
Wear Class 4 arc-flash protection at full voltage
Verify dielectric fluid level before operation
Implement step-test protocol (25%, 50%, 75%, 100%)
Maintenance Schedule
Interval | Procedure | Standard |
---|---|---|
After each use | Visual inspection for damage | ANSI/NETA ETS |
Every 3 months | Dielectric fluid integrity test | IEC 60480 |
Annually | Full calibration and certification | ISO/IEC 17025 |