>800kV Range
LQHVF 1200kV/1200pF 3-Stage Capacitive Voltage Divider & Coupling Capacitor
Breakthrough in Ultra-High Voltage Measurement Technology
The LQHVF 1200kV/1200pF redefines high-voltage testing with its innovative three-stage modular design. Engineered to deliver precision measurements at unprecedented voltage levels, this system combines 400kV-rated modules in series to achieve 1200kV operational capacity with laboratory-grade accuracy and exceptional safety margins.
Technical Specifications
Parameter | Specification | Testing Standard |
---|---|---|
System Configuration | 3 × 400kV stages in series | IEC 61869-11 |
Rated Voltage | 1200kV AC | IEC 60137 |
Stage Voltage | 400kV per module | IEC 60071 |
System Capacitance | 1200pF | IEC 61869-11 |
Frequency | 50Hz | IEEE C57.13 |
Dividing Ratio | 2000:1 | IEC 60044-7 |
Accuracy Class | ≤±1% | Class 0.5 |
Dielectric Loss | <0.2% | ASTM D924 |
Insulation Withstand | 1320kV/1min (110% VR) | IEC 60060 |
Cooling System | ONAN (Oil Natural Air Natural) | IEC 60076-2 |
Three-Stage Modular Design Advantages
Scalable Architecture
Three identical 400kV modules:
Series configuration for 1200kV operation
Each stage independently functional
System capacitance: 1200pF
Advanced Corona Management
Aluminum alloy corona rings:
Ensure discharge-free operation at full voltage
Optimized for transportation efficiency
Scalable HV connections
Measurement Versatility
Multiple configuration options:
Special lead-wire to variable frequency sources
Single-stage (400kV) to full-system (1200kV)
HV corona-free connections
Stable Foundation System
Removable pedestal provides:
Exceptional stability at extreme heights
Rapid assembly/disassembly capability
Wind-resistant design for field testing
Performance Characteristics
Voltage Distribution
Stage | Rated Voltage | Withstand Voltage |
---|---|---|
Stage 1 | 400kV | 440kV |
Stage 2 | 400kV | 440kV |
Stage 3 | 400kV | 440kV |
System | 1200kV | 1320kV |
Accuracy Metrics
Ratio error: ≤±1% (full scale)
Phase displacement: <5 minutes
Temperature coefficient: 3×10-5/°C
Frequency response: 20-300Hz ±1.5%
Safety Margins
110% rated voltage withstand for 1 minute
No abnormal discharge at 1320kV
Double safety margin on mechanical design
Automatic pressure relief system
Transportation & Installation Advantages
Feature | Standard 1200kV Dividers | LQHVF 3-Stage System | Benefit |
---|---|---|---|
Maximum Component Weight | 800-1000kg | 400kg per stage | 60% lighter modules |
Transportation Height | 10-12 meters | 4.5 meters | Standard container compatible |
Assembly Time | 8-10 hours | 3-4 hours | 65% faster deployment |
Configuration Flexibility | Single voltage only | 400kV, 800kV, 1200kV | 3-in-1 system versatility |
Industrial Applications
UHV Transmission Testing
Commissioning of 1100kV+ transmission systems per IEC 62271
Research Facilities
Dielectric strength testing of advanced insulation materials
Power Transformer Certification
Impulse withstand testing at extreme voltages
High-Power Laboratories
Reference standard for calibrating UHV test systems
Compliance & Certifications
IEC 61869-11: Instrument Transformers
IEC 60060-1: High-voltage test techniques
IEEE 4-2013: Standard for HV Testing
EN 50191: Test facility safety requirements
ASTM D924-18: Dissipation factor standard
ISO 9001:2015 Quality Management