100kv ~ 200kV Range
LQHVF 100kV/400pF Capacitor Voltage Divider
Ultra-precise high-voltage measurement solution featuring advanced insulated shell construction and industry-leading<2pc partial="" discharge="" performance.="" engineered="" for="" critical="" applications="" in="" power="" transmission="" testing="">
Technical Specifications
Rated Voltage: 100kV AC RMS
Nominal Capacitance: 400pF
Dividing Ratio: 1000:1 (±1% accuracy)
Frequency: 50/60Hz (45-65Hz operating range)
Dielectric Loss: ≤0.4% @ 25°C
Partial Discharge: <2pC at 100kV
Operating Duration:
60 minutes continuous @ 100% rated voltage
Continuous operation @ 80% rated voltage
Advanced Structural Design
Insulated Shell Construction
Corona Cover: Prevents ionization at HV terminals
Corona Ring: Graded field control for discharge prevention
Capacitor Body: Precision-wound capacitive elements
LV Arm: Shielded low-voltage measurement interface
Composite Insulation: Triple-layer protection against flashover
Safety-Enhanced Features
Integrated Grounding Points: Dual M10 terminals for safety ground
Visual Indicators: Voltage presence warning system
Barrier-Free Design: Eliminates internal discharge paths
Performance Validation
Parameter | Test Standard | Performance |
---|---|---|
Voltage Withstand | IEC 60060-1 | 120kV/1min (120% rated) |
Partial Discharge | IEC 60270 | <1.8pC @ 100kV |
Temperature Rise | IEEE C57.19.00 | 35°C above ambient @ full load |
Linearity Error | IEC 61869-11 | <±0.8% 10-100% range |
Compliance: Meets IEC 61869-11, IEEE C57.13, and ANSI/NETA MTS-2023 standards.
Critical Applications
Power Transmission
EHV substation commissioning
Transformer ratio verification
Switchgear diagnostic testing
Research & Calibration
National standards laboratories
HV equipment certification
Reference divider for meter calibration
Industrial Testing
HVDC converter station maintenance
Generator step-up transformer testing
Cable system commissioning
Operational Advantages
Ultra-Low PD: <2pC ensures measurement integrity in sensitive applications
Insulated Shell Design: Enhanced safety in high-energy environments
Precision Accuracy: ≤±1% measurement uncertainty
Thermal Stability: Maintains accuracy during extended operation
Dual Operation Modes: Flexible for different testing requirements
Installation & Safety Protocol
Mounting Requirements
Foundation: Level surface with vibration isolation
Clearances: 2m radial clearance at full voltage
Grounding: Dual 25mm² copper cables to earth grid
Safety Procedures
Establish safety perimeter per IEEE 516 guidelines
Verify grounding continuity (≤0.1Ω resistance)
Perform three-step verification (30%, 60%, 100% voltage)
Monitor temperature during extended operation
Implement lockout/tagout during maintenance
Maintenance & Calibration
Preventive Schedule
Interval | Procedure | Standard |
---|---|---|
Daily | Visual inspection for contamination | ANSI/NETA ETS |
Quarterly | Dielectric integrity verification | IEC 60480 |
Annual | Full metrology calibration | ISO/IEC 17025 |
Calibration: Recommended with NIST-traceable standards.