High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

100kv ~ 200kV Range

LQHVF 100kV/4000pF Dual-Function Capacitive Divider | 2000:1 Precision & ≤2pC PD

Precision 100kV/4000pF dual-function capacitive divider with 2000:1 ratio and ≤2pC partial discharge. Features removable base, aluminum corona rings, and ONAN cooling for laboratory-grade measurements.


  • US$ 3,203.00
  • Lead time: 30 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHVF 100kV/4000pF Capacitive Voltage Divider & Coupling Capacitor

Dual-function precision instrument combining voltage measurement and power system coupling capabilities. Features industry-leading ≤2pC partial discharge and 2000:1 ratio for critical high-voltage applications in research, calibration, and industrial testing.

Technical Specifications

  • Rated Voltage: 100kV AC RMS

  • Nominal Capacitance: 4000pF ±2%

  • Dividing Ratio: 2000:1 (±1% accuracy)

  • Frequency: 60Hz (50-500Hz optional)

  • Dielectric Loss: <0.2% @ 25°C

  • Partial Discharge: ≤2pC at 100kV

  • Insulation Withstand: 110kV/1min (110% rated voltage)

  • Operating Duration:

    • 60 minutes continuous @ 100% rated voltage

    • Continuous operation @ 80% rated voltage

  • Cooling System: ONAN (Oil Natural Air Natural)

Advanced Structural Design

Dual-Function Architecture

  • Aluminum Corona Rings: Lightweight alloy construction reduces weight while preventing discharge

  • Removable Pedestal: Heavy-duty base with quick-release maintenance access

  • Scalable HV Connections: Corona-free terminals for flexible configurations

  • Modular Design: Field-replaceable components reduce downtime

Precision Measurement System

  • Special Measuring Lead-Wire: Direct interface with variable frequency power sources

  • Dual-Stage Operation: Supports single-stage and series configurations

  • High-Resolution Ratio: 2000:1 division for detailed measurements

Performance Validation

ParameterTest StandardPerformance
Voltage CoefficientIEC 60060-1<0.02%/kV
Partial DischargeIEC 60270≤1.7pC @ 100kV
Temperature StabilityIEC 60270±0.15% capacitance shift (-20°C to +50°C)
Phase ErrorIEC 61869-11<2 minutes at 60Hz

Compliance: Exceeds IEC 61869-11, IEEE C57.13, and ANSI/NETA MTS-2023 standards.

Premium Applications

Calibration Laboratories

  • National standards traceability

  • Reference divider for meter calibration

  • PD measurement system verification

Power Quality Analysis

  • Harmonic distortion measurement

  • Transient overvoltage capture

  • Voltage flicker analysis

High-Energy Research

  • Particle accelerator power systems

  • Plasma confinement experiments

  • Fusion energy test beds

Operational Advantages

  • Ultra-High Precision: 2000:1 ratio enables detailed voltage analysis

  • Dual-Function Design: Combines voltage division and coupling capabilities

  • Exceptional PD Performance: ≤2pC ensures measurement integrity

  • Thermal Management: ONAN cooling maintains stability during extended tests

  • Maintenance Optimized: Removable base reduces service downtime

Connection & Integration

Measurement Configurations

  • Single-Stage Mode: Standard 2000:1 division

  • Dual-Stage Series Mode: Extended range for specialized testing

  • Coupling Capacitor Mode: Power system signal injection

Wiring Protocol

  1. Connect special lead-wire to variable frequency source

  2. Implement HV corona-free connections

  3. Establish dual-point grounding (≤0.1Ω resistance)

  4. Configure for desired measurement mode

  5. Perform step-test (25%, 50%, 75%, 100%)

Safety & Maintenance

Critical Procedures

  • Pre-Operation Check: Verify oil level and grounding integrity

  • Thermal Monitoring: Continuous temperature tracking

  • Discharge Protocol: 5-minute discharge time after operation

  • Preventive Maintenance: Annual dielectric fluid analysis

Calibration Schedule

IntervalProcedureStandard
QuarterlyRatio accuracy verificationIEC 61869-11
BiannuallyPartial discharge recalibrationIEC 60270
AnnuallyFull metrological calibrationISO/IEC 17025

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message