Secondary Switchgear Cabinet
LQXGN2-12 Secondary HV Switchgear: Advanced Protection for 12kV Networks
System Overview
This indoor armored AC metal-enclosed switchgear (IP20) provides complete secondary distribution for 10-12kV networks. Key features include vacuum circuit breakers with 16kA breaking capacity, dual-winding instrument transformers, and integrated protection relays.
Primary Specifications
Parameter | Value |
---|---|
Rated Voltage | 10kV |
Rated Current | 630A |
Short-Time Withstand | 16kA |
Control Voltage | AC 220V |
Enclosure Type | Armored Metal-Clad |
Protection Rating | IP20 |
Core Components
Vacuum Circuit Breaker
Rated Voltage: 12kV
Rated Current: 630A
Breaking Capacity: 16kA
Voltage Transformer
Type: Epoxy Cast / Full Insulation
Rated Voltage: 10kV
Ratio: 10kV/100V
Accuracy: Class 0.5
Current Transformer
Type: Epoxy Cast
Rated Voltage: 10kV
Ratio: 150A/5A/5A (dual secondary)
Accuracy: Class 0.5
Isolation Switch
Rated Voltage: 10kV
Max Voltage: 12kV
Thermal Stability (4s): 12.5kA
Dynamic Stability: 31.5kA
Circuit Resistance: <60 μΩ
Auxiliary Switch
Rated Voltage: 12kV
Rated Current: 630A
Protection & Control Features
Multi-Stage Protection: Overcurrent + Overvoltage + Fast Trip (≤2 cycles)
Dual Control Modes: Local manual operation + Remote SCADA control
Measurement System: Integrated meters for V/I/PF monitoring
Safety Interlocks: Mechanical locking between isolator and breaker
Visual Indicators: LED status lights for circuit conditions
Design Advantages
Armored Construction
Zinc-plated steel compartmentalization contains arc faults per IEC 62271-200 Annex AA
Modular Components
Draw-out breaker design enables maintenance without de-energization
Dual Secondary Windings
Independent 5A outputs for protection relays and metering equipment
Typical Applications
Industry | Application |
---|---|
Industrial Plants | Main secondary distribution for 10kV incomers |
Commercial Complexes | HV/LV interface protection |
Power Generation | Auxiliary system protection for turbines |
Infrastructure | Tunnel ventilation power control |
Testing & Certification
Dielectric test: 28kV AC for 1min (IEC 60060-1)
Short-circuit test: 16kA/1s (IEC 62271-100)
Temperature rise test: 65K max @ 630A (IEC 60298)
Mechanical endurance: 10,000 operations