<100kVA Range
LQLVF 80kVA/2×210.5A Single-Phase Power Noise Filter with ONAN Cooling
Ultra-Low PD EMI Suppression for High-Current 60Hz Systems
Engineered for demanding industrial power systems, the LQLVF 80kVA/2×210.5A Power Noise Filter delivers exceptional electromagnetic interference suppression with ultra-low <2pC partial discharge. Featuring dual 210.5A circuits, ONAN cooling technology, and optimized for 60Hz operation, this high-capacity solution maintains stable 0.38kV symmetric performance during 60-minute continuous full-load operation.
Technical Specifications
Parameter | Specification |
---|---|
Rated Power | 80kVA |
Phase Configuration | Single-Phase |
Frequency | 60Hz |
Cooling System | ONAN (Oil Natural Air Natural) |
Input Voltage | 0.38kV |
Output Voltage | 0.38kV |
Rated Current | 210.5A × 2 Independent Circuits |
Partial Discharge Level | <2pC at rated voltage |
Continuous Operation | 60 min at 100% rated voltage/current |
Performance Highlights
Ultra-Low Partial Discharge
Maintains <2pC PD level at full 0.38kV operation - exceeding IEC 60270 Class II requirements for sensitive industrial systems.
High-Current Capacity
Dual 210.5A circuits support extreme industrial loads with <1% voltage drop during continuous operation.
Optimized 60Hz Performance
Specialized design for North American 60Hz power systems with enhanced harmonic suppression.
Design Advantages
Precision Voltage Symmetry: Identical 0.38kV input/output maintains system stability
Thermal Stability: ONAN cooling ensures safe operation during 60-minute full-load runs
High Power Density: 80kVA capacity in compact footprint
Low-Noise Operation: <2pC PD protects sensitive measurement equipment
Industrial Applications
Industrial motor control centers (60Hz regions)
High-power plastic injection molding machines
Large-scale industrial compressors
Mining equipment power systems
Industrial electrolysis plants
Heavy manufacturing process lines
Key Benefits
Premium PD Performance: Industry-leading <2pC partial discharge at full load
High-Current Capability: 210.5A per circuit capacity
Thermal Reliability: Certified 60-minute continuous operation at 100% load
60Hz Optimization: Enhanced performance for North American power systems
Installation & Operation
Thermal Management
Maintain 150mm top clearance for heat dissipation
Maximum ambient temperature: 45°C
Vertical mounting orientation required
Electrical Integration
Use 150mm² copper conductors for main connections
Terminal torque: 65Nm (per IEC 60947-1)
Ground with 35mm² cable (resistance <0.5Ω)
Balance load across both circuits
Commissioning Tests
Verify PD level at 0.38kV operational voltage
Perform 60-minute full-load thermal stability test
Check oil level indicator before operation
Why This Filter Stands Out
Industry-Leading Current Rating: 210.5A per circuit capacity
Certified Continuous Operation: 60-minute full-load capability
Ultra-Low PD Guarantee: <2pC partial discharge at operational voltage
Specialized 60Hz Design: Optimized for North American power systems
Maintenance Protocol
Annual oil dielectric test (per ASTM D877)
Biannual thermal imaging during operation
PD verification every 24 months
5-year comprehensive performance validation
Compliance & Standards
IEC 60270: Partial discharge measurements
IEEE C57.106: Insulating oil maintenance
UL 508: Industrial control equipment standards
CSA C22.2 No. 14: Industrial control equipment
RoHS 3 (2015/863/EU) compliant