<100kVA Range
LQLVF 50kVA/2×125A High-Voltage Power Noise Filter
Premium EMI Suppression for 3kV Power Systems
Engineered for critical high-voltage applications, the LQLVF 50kVA/2×125A Power Noise Filter delivers exceptional electromagnetic interference suppression in 3kV systems. Featuring ultra-low <2pC partial discharge, dual 125A circuits, and transformer-matched operational lifespan, this industrial-grade solution provides >60dB attenuation while maintaining robust 5kV/1min insulation integrity.
Technical Specifications
| Parameter | Specification |
|---|---|
| Rated Power | 50kVA |
| Rated Voltage | 3kV/3kV |
| Rated Current | 125A × 2 Independent Circuits |
| Frequency Range | 50-60Hz |
| Quality Factor (Reactor) | >70 |
| Background PD Level | <2pC |
| Attenuation | 40-100kHz: >40dB 100kHz-1MHz: >60dB |
| Insulation Level | 5kV/1min |
| Operating Profile | Continuous operation matching transformer duty cycle |
| Weight | 280kg (robust industrial construction) |
Performance Highlights
Ultra-Low Partial Discharge
Maintains <2pC background PD level - exceeding IEC 60270 Class II requirements for high-voltage systems.
High-Voltage Capability
Designed for 3kV systems with 5kV/1min insulation withstand - ideal for industrial substations.
Transformer-Matched Operation
Continuous duty rating synchronized with connected transformers for 25+ year service life.
Robust Industrial Design
Heavy-Duty Construction: 280kg ruggedized design for vibration resistance
Thermal Management: Natural convection cooling for maintenance-free operation
Switchgear Integration: Pre-engineered for sub-stage cabinet installation
High Reactor Efficiency: Quality factor >70 ensures minimal energy loss
Industrial Applications
Medium-voltage industrial substations
Transformer-coupled power systems
Process industry power distribution
High-voltage test laboratories
Critical infrastructure protection systems
Key Advantages
Extended Operational Lifespan: Matches 25+ year transformer service life
Premium PD Performance: <2pC partial discharge for sensitive HV equipment
High Power Handling: 50kVA capacity with 125A per circuit
Enhanced Safety: 5kV/1min insulation exceeds IEC 60664-1 requirements
Installation Guidelines
Structural Requirements:
Cabinet floor rating ≥350kg/m²
Minimum clearance: 100mm sides, 150mm top
Electrical Connections:
Use 70mm² copper conductors
Terminal torque: 50Nm
Ground with 35mm² minimum cable (resistance <0.5Ω)
Commissioning Tests:
Partial discharge test at 3.6kV AC (<2pC verification)
Insulation resistance test at 5kV DC (min 1GΩ)
Attenuation verification with spectrum analyzer
Why This Filter Stands Out
High-Voltage Specialization: 3kV rating with 5kV insulation margin
Extended Service Life: Transformer-matched operational profile
Ultra-Clean Power: <2pC PD level protects sensitive equipment
Industrial Reliability: 280kg rugged construction for harsh environments
Compliance & Standards
IEC 60270: Partial discharge measurements
IEC 61000-6-2: Industrial immunity standards
IEC 61000-6-4: Industrial emissions standards
IEEE C57.12.90: Transformer test standards
RoHS 3 (2015/863/EU) compliant